beautypg.com

Spectrum Controls 140 AUI 040 00sc User Manual

Page 7

background image

Quantum Series 140 AUI 040 00sc

8

1.1

Inputs

The 16 Channels are separated into four groups of four. Each group can be configured for a different voltage,
current range, resistance, thermocouple and RTD range. The ranges available are as follows:

Current Ranges

• 4 to 20 mA, 0 to 20 mA, ±20mA

Voltage Ranges:

• ±0.05VDC, ±0.5VDC, ±2.0VDC, ±5VDC, ±10VDC, 0-10VDC, 0-5VDC, 1-5VDC

Resistance Ranges

• 150, 490, 980, 3000 ohm

Thermocouple Types

• Type J, K , T, E, R, S, B, N

RTD Types

• 100, 200, 500 and 1K

Pt Alpha 385,

100, 200, 500, and 1K

Pt Alpha 392,

100, 200, 500, and 1K

Nickel,

10

Copper 426,

120

Nickel 672, 604

Nickel/Iron 518.

The module can provide data to the PLC in the following formats:

• 12 bit (0 to 4095)

• signed 15 bit (-32768 to +32767)

• unsigned 16 bit (0 to 65535)

• DVM (0 to 10000)

Input Resistance

10M

nominal (Voltage)

250