Quantum Series 140 AUI 040 00sc
44
Fault LED -
1 Red LED indicates a module self test error, or fatal H/W error. A blink code will be defined that will
indicate the type of self test error. Count the number of blinks before a pause to determine the error code in
the table below.
Fault LED Blink Code
Blink # Fault
1
ROM CRC Error
2
EEPROM Error
3
RAM Error
4
Autocal Error
5
Watchdog Timer Error
6
CPU Error
7
DPM Error
Channel LED -
32 Green LEDs indicates the channel is enabled and a valid input signal level is present. The LED is off if the
channel is disabled. A blinking LED indicates that the channel has exceeded a range limit.
STEP 4: Check the module’s communication status.
VERIFY: The module’s green ACTIVE LED is on. This indicates that the module is communicating properly
with the rack.
CORRECTIVE ACTION:
• Set the rack into run mode.
• Reinstall the module in the rack.
STEP 5: Check the module’s health status.
VERIFY: The module is reported as healthy in the Modsoft I/O map Screen. Check to make sure that the
module description, slot location, and register assignments are correct. Also, verify that the module is recog-
nized and reported as healthy. If an asterisk is present before the module’s name, then the module is not
recognized by the rack.
CORRECTIVE ACTION:
• Reinstall the module in the rack.
• Reselect the module in the I/O Map using the
files included with your module.
STEP 6: Check the module’s register operation.
VERIFY: The 4X configuration word and the 3X+8 Status word are setup properly. As a quick check,
disable all ladder programming and set the 4X register to 0000 Hex and verify that the 3X+8 Status register
cycles through the values 0000, 0001, 0010, and 0011 Hex.