Agency certifications, Ii 3g – Spectrum Controls 1734sc-IF4U User Manual
Page 45

Appendix A: IF4U Specifications
A-5
User’s Manual Pub. 0300266-01 Rev. A
Environmental Tests
Industry Standards
Test Level Limits
Conducted RF immunity
(Performance Criteria A)
IEC 61000-4-6
Rockwell Document QTP#X0327
10V rms with 1kHz sine wave
80%AM from 150kHz to 80MHz
on signal and power ports
Magnetic Field
(Performance Criteria A)
IEC 61000-4-8
Rockwell Document QTP#X0327
30Arms/m
AC Mains Voltage Dips,
Interruptions and Variations
IEC 61000-4-11
Rockwell Document QTP#X0327
Follow the 61000-4-11.
Lead Resistance used in 3
and 4-wire accuracy tests
In-house
2 Ohms maximum (equivalent to
300 ft., 18AWG)
Agency Certifications
The following certifications will be obtained at 1st production release.
UL 508
ISA
12.12.01
CUL
Operating Temperature Code T6
CE compliance to EN 61010-1 and EN 61131-2
Atex 4.4
ODVA DeviceNet Compliance
ATEX Special Conditions for Safe Use
Provisions shall be made to prevent the rated voltage being exceeded by the
transient disturbances of more than 140%.
The system shall be mounted in an ATEX certified enclosure with a minimum
ingress protection rating of at least IP54 as defined in IEC60529 or EN60529
and used in an environment of not more than pollution degree 2.
These modules must be used with the ATEX certified terminal module 1734-TB
by Allen-Bradley.
-20C < Ta < 55C
DEMKO 12 ATEX 1206052U
EX nA IIC Gc
II 3G