Spectrum Controls 1734sc-IF4U User Manual
Page 23

User’s Manual Pub. 0300266-01 Rev. A
Chapter 3
Configuring the 1734sc-IF4U
Using RSLogix 5000
This chapter covers the following subjects:
Things you should know
About Communications
Use Generic Profile
Use AOP (Add On Profile)
Module configuration
Reading input data
Module update time
Section 3.1
Introduction
This chapter will describe how to configure the IF4U module using RSLogix 5000
programming software.
Section 3.2
About
Communications
The module produces and consumes data as follows:
IF4U Produce/Consume Data
Instance:
Description:
Total Size:
100
Analog Only
16 Bytes RSL5K (Dnet 12 bytes)
Bit
15 14 13 12
11
10 09 08 07 06 05 04
03
02 01 00
Analog
data
12 bytes
0x00-
0x0B
Channel 0 Data - INT
Channel 1 Data - INT
Channel 2 Data - INT
Channel 3 Data - INT
Status Byte for Channel 1
Status Byte for Channel 0
n/a n/a n/a OC OR UR n/a CF n/a n/a n/a OC OR UR n/a CF
Status Byte for Channel 3
Status Byte for Channel 2
n/a n/a n/a OC OR UR n/a CF n/a n/a n/a OC OR UR n/a CF