Spectrum Controls 1734sc-IF4U User Manual
Page 24
3-2
Point IO™ 4 Channel Universal Analog Input Module
User’s Manual Pub. 0300266-01 Rev. A
!
Attention
The IF4U module is not compatible with the 1734-ADN, ADN(X), and
PDN device net adapters and the 1734-APB profibus adapter.
!
Attention
The 1734sc-IF4U is not field upgradable.
!
Attention
The ControlNet adapter (1734-ACNR) has a maximum data transmit
limit of 600 bytes. Therefore, the maximum number of 1734sc-IF4U
modules that can be installed behind a ControlNet adapter is 14.
Section 3.3
Use Generic
Profile
The generic point IO module profile can be used to represent the IF4U module within
RSLogix 5000. The generic profile should be used for RSLogix 5000 versions 14 and
older. Before the generic profile can be added to the IO configuration, the proper
communication module needs to be added to the IO configuration first. Follow the
procedure below to add a communication module to RSLogix 5000.
1.) Add the new local communication module to your project.
2.) Configure the local module, including:
a. Naming the module
b. Choosing a Communication Format
c. Setting the Revision level
d. Setting the module location as necessary such as the slot number for a
1756-CNB module
e. Choosing an Electronic Keying method
3.) Add the new remote module to your project, such as a 1734 Control Net adapter
or Ethernet Adapter (i.e. 1734-ACNR or 1734-AENT, respectively).
4.) Configure the remote module similarly to the local module
5.) Download the configuration to the controller
Note: If you are using Control Net, you must schedule the network using
“RSNetworks for Control Net” after adding the local and remote
communication modules.
Note: When you create a new RSLogix 5000 project with the CompactLogix
1769-L32C or L35CR controller, The Controller Organizer creates a Control
Net port in the local chassis. In this case, you don’t need to add a separate
local communication module.