Environmental specifications – Spectrum Controls 1734sc-IF4U User Manual
Page 44
A-4
Point IO™ 4 Channel Universal Analog Input Module
User’s Manual Pub. 0300266-01 Rev. A
Environmental Specifications
Environmental Tests
Industry Standards
Test Level Limits
Temperature (Operating)
(Performance Criteria A)
IEC60068-2-1: (Test Ad, Operating Cold),
IEC60068-2-2: (Test Bd, Operating Dry Heat),
IEC60068-2-14: (Test Nb, Operating Thermal
Shock)
0°C to +55°C
Temperature
(Non-operating)
(Performance Criteria B)
IEC60068-2-1:
(Test Ab, Unpackaged Non-operating Cold),
IEC60068-2-2:
(Test Bb, Unpackaged Non-operating Dry Heat),
IEC60068-2-14:
(Test Na, Unpackaged Non-operating Thermal
Shock)
-40°C to +85°C
Operating Altitude
2000 meters (6561 feet)
Not tested
Humidity (Operating)
(Performance Criteria A)
IEC60068-2-30:
(Test Db, Unpackaged Damp Heat):
5% to 95% non-condensing
Vibration (Operating)
(Performance Criteria A)
IEC60068-2-6: (Test Fc, Operating)
5G @ 10Hz to 500Hz, 0.030in.
max. peak-to-peak
Shock (Operating)
(Performance Criteria A)
IEC60068-2-27: (Test Ea, Unpackaged Shock)
30g,11ms half-sine (3 mutually
perpendicular axes)
Shock (Non-operating)
(Performance Criteria B)
IEC60068-2-27: (Test Ea, Unpackaged Shock)
50g, 11ms half-sine (3 mutually
perpendicular axes)
Radiated Emissions
CSIPR 11; Group 1, Class A
Rockwell Document QTP#X0327
(Enclosure) Class A, 30MHz to
1GHz
Conducted Emissions
IEC 61000-6-4:2007
Rockwell Document QTP#X0327
Group 1, Class A (AC Mains),
150kHz – 30MHz
ESD immunity
(Performance Criteria B)
IEC 61000-4-2
Rockwell Document QTP#X0327
6kV Indirect (Coupling Plate)
6kV Contact Discharge (to points
of initial contact)
8kV Air Discharge (to points of
initial contact)
Radiated RF immunity
(Performance Criteria A)
IEC 61000-4-3: Level 3
Rockwell Document QTP#X0327
10V/M with 1kHz sine-wave
80% AM from 80MHz to
2000MHz
10V/M with 200Hz sine-wave
50% Pulse 100% AM @900MHz
10V/M with 200Hz sine-wave
50% Pulse 100%AM
@1890MHz
1V/M with 1kHz sine-wave
80%AM from 2000MHz to
2700MHz
(3V/M goal)
EFT/B immunity
(Performance Criteria B)
IEC 61000-4-4*
Rockwell Document QTP#X0327
Signal Ports:
±3kV @ 5kHz for 5 minutes,
Criteria B
±2kV @ 5kHz for 5 minutes,
Criteria A
±2kV @ 5kHz for 5 minutes,
Criteria B (standard)
Power Ports:
±2kV @ 5kHz for 5 minutes,
Criteria A
±2kV @ 5kHz for 5 minutes,
Criteria B (standard)
Surge transient immunity
(Performance Criteria B)
IEC 61000-4-5
Rockwell Document QTP#X0327
Signal Ports:
±2kV line-earth {CM}@ 2Ω on
shielded ports
Power Ports
±2kV CM @ 12Ω
±1kV DM @ 2Ω