Chapter 1: Module Overview

1-5

User’s Manual Pub. 0300266-01 Rev. A

1.6.1 Module Power-up

At power-up, the module performs a check of its internal circuits, memory, and basic
functions. If no faults are found during power-up diagnostics, the module status LED is
turned on.
After power-up checks are complete, the module waits for valid channel configuration
data. If an invalid configuration is detected, the module will generate a PLC fault. Once
a channel is properly configured and enabled, it continuously converts the input data to a
value within the range selected for that channel.

1.6.2 Module Operation

The 1734sc-IF4U module provides four independent analog input channels. Each
channel includes four selectable filter settings and can be configured for voltage,
thermocouple, current, resistance or RTD input types.
The 1734sc-IF4U module utilizes a 20-bit Sigma-Delta ADC (Analog to Digital
Converter) to achieve 18-bit resolution. Inputs to the ADC are first multiplexed through
analog switches then buffered by a precision, low offset and drift, programmable gain
amplifier. The ADC also provides the programmable current source used in resistive
measurements.
The 1734sc-IF4U plug-in module communicates over its isolated CAN Bus interface
through the module backplane. The 1734 network adapter then communicates to the PLC
controller. See the block diagram below.

+24VDC

+3.3VDC ±2%

‐15VDC ±3VDC

GND

Isolated

CAN Bus

CAN 

Bus
and 

+5VDC

ADC

SPI Interface

Voltage / Current (4‐chs)

RTD / Resistance (2/4‐chs)

Thermocouple (3‐chs)

GND

Analog_1

Analog_0

I

s

o

l

a

t

i

o
n

Point Bus

LEDs

Processor

Isolation

Barrier

Controls and Status

Controls

Notes:

1) I/O’s are ESD protected

CJC (1‐ch)

Analog_2

Protection,

Filtering,

Analog

Switch

Matrix,

PGA

+15VDC ±3VDC

Current Srcs

PGA_Interrupt

Low

Input‐Power

Interrupt

and

System_Reset

SPI Interface

Power Supplies

And

Power Monitor

Isolation

Barrier

CLK

System 

Clock

Generator