1-4

Point IO™ 4 Channel Universal Analog Input Module



User’s Manual Pub. 0300266-01 Rev. A

Indicator State

Description

Flashing
Green

Device needs commissioning due to configuration missing,
incomplete, or incorrect.
NOTE: The module always sets default values for invalid
configurations. Therefore, this status will not be shown.

Flashing Red Not used with this module.

Solid Red

Recoverable fault.
ADC communications fault, or backplane communications
error.

Flashing
Red/Green

Device is in self-test mode.
This is only used during factory test and power-up.

Channel
Status

Off

Channel disabled. Will remain off after power-up until
connection established. Analog processing will not take place
if no connection is made.

Solid Green

Normal (channel scanning inputs)

Flashing
Green

Calibration mode.

Solid Red

Major channel fault.
ADC communications fault.
Analog values will remain at current state until fault has
recovered.

Flashing Red Channel at end of range

Flashing
Red/Green

Displayed during power-up.

Network
Status

Off

Device not powered/Not online.

Solid Green

Device operational AND online AND connected.

Flashing
Green

Device operational AND online but not connected.
-OR-
Device online AND device needs commissioning.

Flashing Red

Minor fault AND/OR connection timeout AND/OR no
network power.

Solid Red

Critical fault OR critical link failure.

Flashing
Red/Green

Communication faulted and received an identify comm fault
request - long protocol.
Also displayed during power-up.

Section 1.6
System
Overview

The module communicates to the controller via a 1734 Control Net, Device Net or
Ethernet adapter. The module receives 5 and 24V dc power through the bus interface.