SOR TA Nuclear Qualified Pressure Switch User Manual
Pressure switches, Nuclear-qualified, General instructions
Form 654 (04.13) ©SOR Inc.
1/4
Pressure
Nuclear-Qualified
Pressure Switches
General Instructions
NOTE: If you suspect that a product is defective, contact the factory or the SOR
®
Representative
in your area for a return authorization number (RMA). This product should only be installed by
trained and competent personnel.
Installation
Design and specifications are subject to change without notice.
For latest revision, go to www.sorinc.com
The vent connection must be plugged or vented to dry
atmosphere as
required by application requirements. Test Data Sheet
SOR form # 716
is supplied for each serial number and provides switch
performance data in
the vented and plugged condition.
Failure to mount the housing on
a fl at mounting surface may
result in torsional forces on the
housing that could cause false trips or
render the pressure switch inoperative.
Process Connection
Electrical Connection
Securely connect process line to pressure port using two wrenches: one to hold hex flats on
pressure port, the other to tighten process pipe or tube fitting.
Be certain the process connection is tightened and positioned so bending
and torsional forces imposed on pressure switch are minimal. Use care
not to loosen pressure port from body or body from housing.
Electrical connections are
marked on the insulation of
the wire leads. Conduit should
be installed without applying
strain to the housing.
SPDT
DPDT
Vacuum switches only
Vacuum