Typical wiring diagram, For other diagrams, consult our customer service, Page 4 – IOTA ILB-1826 User Manual
Page 4
![background image](/manuals/738121/4/background.png)
Page 4
TYPICAL WIRING DIAGRAM
For other diagrams, consult our Customer Service.
RED
RED
EMERGENCY LED
DRIVER
STANDARD LED
DRIVER
COMMON
RED/WHT
BLUE
BLK/ORG
120V (BLK)
277V (ORG)
RED OR RED BLK (+)
WHT/RED
WHITE (-)
RED
BLACK (-)
RED (+)
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND AC POWER IS SUPPLIED.
ч
ч
ш
BLK/ORG LEAD FOR COLD-WEATHER UNIT ONLY.
FOR NON-COLD WEATHER UNITS, CAP BLK/ORG LEAD.
FOR COLD-WEATHER UNIT 120V INSTALLATION, CONNECT BLK/ORG TO BLK.
FOR COLD-WEATHER UNIT 277V INSTALLATION, CAP BLK/ORG AND BLK SEPARATELY.
ø
ILB-3020 AND ILB-3020-CW
SELECT PROPER LOAD
REQUIREMENT. SINGLE WIRE
FROM STD DRV ONLY (BLUE)
UNIT
CONNECTOR
*EMERGENCY OPERATION
TEST ACCESSORY LEADS-OBSERVE PROPER
POLARITY WIRING.
ù
#1
#2
BATTERY PACKS
20W LED
ù
WHITE
TEST
SWITCH
BLACK
SWITCHED OR
UNSWITCHED LINE
20W LED
20W LED
20W LED
20W LED*
COMMON
OPTIONAL CONNECTOR FOR COLD-WEATHER
HEATING BLANKET ONLY. FOR NON-COLD-WEATHER
UNITS, LEAVE DISCONNECTED.
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD.
UNSWITCHED LINE
RED (+)
68018-041