beautypg.com

Operation, Testing & maintenance, Installing the charge indicator – IOTA ICE-420-EM-B User Manual

Page 3: Installing the test switch, Labels, Completing installation

background image

Page 3

4. INSTALLINg ThE ChARgE INDICATOR

Select a convenient location on the fixture so that the

Charge Indicator can be seen after installation. Allow for

proper clearance and drill or punch a ½

″ mounting hole. Disconnect the leads from the Charge Indicator and

push the

Charge Indicator into the ½

″ hole until it is firmly locked into place. Reconnect the leads, observing

proper polarity (Red/Black or Red lead w/connector to positive (+) red tab). Make certain all leads are enclosed in

an appropriate wireway. Refer to Illustration 1.
NOTE: For proper operation, use only the test accessories provided with the unit. See Page 1 of the Instruction

Manual.

5. INSTALLINg ThE TEST SWITCh

The

Test Switch should be mounted on the fixture to allow access to authorized personnel. Drill or punch a ½

mounting hole. Make certain all leads are enclosed in an appropriate wireway. Refer to Illustration 1.

6. LABELS

Attach the appropriate labels adjacent to the

Test Switch and Charge Indicator. Annotate Re-lamping label for

lamp type and wattage. The Caution and the Re-lamping labels must be on the fixture in a readily visible location

to anyone attempting to service the fixture.

7. COMPLETINg INSTALLATION

A. When the installation is complete, switch the A.C. power on and join the

ICE-420-EM-B unit connector.

B. Replace the ballast cover, fixture lens and other fixture hardware.

OPERATION

General – This unit is primarily designed to be used with compact fluorescent lamp downlight fixtures. It will wire in

conjunction with the existing A.C. ballast(s) and lamp(s) to provide the emergency function. It can also be wired for
emergency only operation.
Normal Mode – A.C. power is present. The A.C. ballast operates the fluorescent lamp(s) as intended. The ICE-420-EM-B

is in the standby charging mode. The

Charge Indicator will be lit providing a visual indication that the battery is being

charged.
Emergency Mode – The A.C. power fails. The ICE-420-EM-B senses the A.C. power failure and automatically switches

to the Emergency Mode. One lamp or two lamps are illuminated, at reduced output, for a minimum of 90 minutes. When

the A.C. power is restored, the

ICE-420-EM-B switches the system back to the Normal Mode and resumes battery

charging. See page 1 of the Instruction Manual.

TESTING & MAINTENANCE

Pressing the

Test Switch turns off the light on the Charge Indicator and forces the unit into emergency mode, inter-

rupting power to the designated A.C. ballast. The emergency lamp is now being lit by the

ICE-420-EM-B unit. After

releasing the

Test Switch, the fixture returns to normal operation after a momentary delay. To simulate a “BLACK OuT”

use the circuit breaker to turn off A.C. power.

Initial Testing – Allow the unit to charge approximately 1 hour, then conduct a short discharge test by depressing the

Test Switch. Allow a 24 hour charge before conducting a one hour test.

The

ICE-420-EM-B is a maintenance free unit, however, periodic inspection and testing is required. NFPA 101, Life

Safety Code, outlines the following schedule:

Monthly – Insure that the Charge Indicator light is illuminated. Conduct a 30 second discharge test by depressing the

Test Switch. One lamp or two lamps should operate at reduced output.

Annually – Insure that the Charge Indicator light is illuminated. Conduct a full 1½ hour discharge test. The unit should

operate as intended for the duration of the test.

“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”

SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.

Consult Customer Service or visit www.iotaengineering.com for current warranty information.