INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the
I-13-EM-J unit connector is disconnected.
1. MOUNTINg ThE I-13-EM-J
When used with ceiling mounted downlight fixtures, the
I-13-EM-J should be mounted on the fixture above
the ceiling.
When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between
the battery pack and the lamp.
2. MOUNTINg ThE TEST SWITCh AND ChARgE INDICATOR LIghT
Cut a single gang switch box into the ceiling tile adjacent to the fixture within reach of the
I-13-EM-J flex. After
mounting the switch box, connect flex to the box and route all leads inside the box. Connect the leads to the com-
ponents as follows:
Red lead
(+) Charge light terminal
Wht/Red lead (–) Charge light terminal
White
Test
switch
*Wht/Blk
lead
Unit
connector
White/Black
*Wht/Blk lead Unit connector
* To prevent electrical shock and unintentional battery discharge, do not join the unit connector until the installation
is complete.
NOTE: To ensure proper operation, use only the test accessories provided with the unit. See Page 1 of the Instruc-
tion Manual.
3. WIRINg
A.
The
I-13-EM-J and A.C. ballast must be on the same branch circuit.
B.
The
I-13-EM-J requires an unswitched A.C. power source of either 120 or 277 volts; therefore, when used with
switched fixtures, the
I-13-EM-J input must be wired ahead of the switch.
C. Refer to the wiring diagrams on the back page for the proper wiring.
4. LABELS
Attach the appropriate labels adjacent to the
Test Switch and Charge Indicator. Annotate Re-lamping label for
lamp type and wattage. The Caution and the Re-lamping labels must be on the fixture in a readily visible location
to anyone attempting to service the fixture.
5. COMPLETINg INSTALLATION
When the installation is complete, switch the A.C. power on and join the
I-13-EM-J unit connector.
INSURE WIRING IS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS.