Installation instructions, Lamps operated, Mounting the i-320 – IOTA I-320 User Manual
Page 2: Wiring, Installing the threaded body test switch (tbts), Wiring the a.c. input, Illustration 1 recessed troffer fixture, Illustration 2 strip fixture
![background image](/manuals/738074/2/background.png)
Page 2
INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the I-320 unit connector is disconnected.
1. LAMPS OPERATED
2. MOUNTING THE I-320
Remove the ballast channel cover. Mount the
I-320 in the ballast channel at least
1
/
2
″ away from the A.C. ballast(s).
When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between
the battery pack and the lamp.
3. WIRING
Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance
with the National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.
4. INSTALLING THE THREADED BODY TEST SWITCH (TBTS)
Recessed Troffer Fixture – Select a convenient location with proper clearance in the ballast cover and drill or
punch a
7
/
8
″ hole (
1
/
2
″ knockout). Insert the
7
/
8
″ bushing into the hole. Push the plastic tube through the bushing.
Route the leads of the
TBTS through the plastic tube. Connect the LED wires from the unit to the TBTS (Red/Black
or Red w/tag to Red, White/Red to White). Push the entire assembly back into the tube until the lens collar rests
against the plastic tube. The plastic tube should be adjusted so that the
TBTS is within ¼
″ of the fixture lens. The
TBTS must be visible after installation. Refer to Illustration 1.
Strip Fixture – Select a convenient location on the fixture so the
TBTS can be seen after installation. Allow for
proper clearance inside the fixture and drill or punch a
1
/
2
″ hole. Remove the nut from the TBTS. Push the TBTS
housing into the
1
/
2
″ hole and secure with the nut. Connect the LED wires from the unit to the TBTS (Red/Black or
Red w/tag to Red, White/Red to White). Refer to Illustration 2.
ATTENTION: Only connect the I-320 to the TBTS LED supplied with the unit. The LED must be replaced
when replacing the unit.
5. WIRING THE A.C. INPUT
A.
When
the
I-320 is installed on the same branch circuit, refer to Illustration 3, Figures A and B for input wiring.
When installed on separate branch circuits, refer to Illustration 3, Figures C and D for input wiring. Per NEC, the
I-320 and A.C. ballast must be on the same panel board.
B.
The
I-320 requires an unswitched A.C. power source of either 120 or 277 volts; therefore, when used with
switched fixtures, the
I-320 input must be wired ahead of the switch. Refer to Illustration 3 for switched and un-
switched fixture wiring diagrams.
C. Refer to the wiring diagrams on the back page for the proper wiring. For wiring diagrams of ballasts not shown,
consult our Customer Service.
7/8" BUSHING
FIXTURE
BALLAST CHANNEL COVER
PLASTIC TUBE
TBTS
FIXTURE LENS
Illustration 1 Recessed Troffer Fixture
FIXTURE
TBTS
+ RED
LEAD
WHITE
LEAD
Illustration 2 Strip Fixture
I-320
OBSERVE PROPER POLARITY
OPTION
LAMP TYPE
EMERGENCY
OPERATION
*VIOLET LEADS
1
2
3
4
2´-4´ T8 Single Pin & Bipin
2´-4´ 28W or 54W T5
One Lamp
One Lamp
Connected
Disconnected
2´-4´ 14W-24W, 39W T5
One Lamp
Connected
13W-32W 4-Pin Compact
One Lamp
Connected
5
42W 4-Pin Compact
One Lamp
Disconnected
I-320
The
I-320 can be used with most
2
′–4′ lamps. Refer
to the chart on the right for the type of lamp
operated in emergency mode. Contact Customer Ser-
vice for answers about specific lamps.
*The 6
″ violet leads provide the lamp selection option.
The unit is shipped from the factory with the leads
disconnected and capped. When used with particular
lamp types, violet leads should be connected to one