Maintenance – Glow-worm Clearly Hybrid - Compact System User Manual
Page 32
0020096883_01 - 06/10 - Glow-worm
- 30 -
MAINTENANCE
15.2.1
System fault codes
Fault
codes
Description
Cause
Solution
001
Failure in Ebus communication between with the
boiler
The boiler is not connected to the control
unit.
The cable polarity is reversed.
The boiler is off.
Check that the boiler is connected to the
control unit.
Check the connection’s + / - polarity.
Ensure that there is no interruption to the
electricity network and that the boiler is
properly connected and turned on.
002
Failure in Ebus communication between with the
heat pump
The heat pump is not connected to the
control unit.
The heat pump is off.
Make sure the heat pump is connected to
the control unit.
Ensure that there is no interruption to the
electricity network and that the heat pump
is properly connected and turned on.
003
Failure in Ebus communication between with the
hydraulic module
The hydraulic module is not connected to
the control unit.
The hydraulic module is off.
Make sure that the hydraulic module is
connected to the control unit.
Ensure that there is no interruption to the
electricity network and that the hydraulic
module is properly connected and turned
on.
010
Heating circuit fl ow temperature sensor failure
(open circuit)
The sensor is defective or not
properly connected to the control unit
management or hydraulic module.
Check the sensor’s connections.
Verify that the position and the operation
of the sensor are correct.
Check the sensor’s resistance.
011
Heating circuit fl ow temperature sensor failure
(short circuit)
The sensor is shorted.
012
Heating circuit fl ow temperature sensor failure low
temperature (open circuit)
The sensor is defective or not properly
connected to the control unit.
Check the sensor’s connections.
Verify that the position and the operation
of the sensor are correct.
Check the sensor’s resistance.
013
Heating circuit fl ow temperature sensor failure low
temperature (short circuit)
The sensor is shorted.
014
Domestic water tank temperature sensor failure
(open circuit)
The sensor is defective or not properly
connected to the control unit.
Check the sensor’s connections.
Verify that the position and the operation
of the sensor are correct.
Check the sensor’s resistance.
015
Domestic water tank temperature sensor failure
(short circuit)
The sensor is shorted.
021
Pressure too low <0.5 bar
There is a leak in the heating circuit.The
venting was not carried out correctly.
Check that there are no leaks.
Drain the heating circuit. Remove air.
Fill the installation.
030
Failure in communication with the zone 1 wireless
room thermostat.
The room thermostat is too far from the
control unit.
There is a problem with the batteries in
room thermostat.
Check the RF signal quality via the
Climapro2 RF installer menu.
Check the location of the thermostat.
Check that the thermostat’s batteries are
installed in their compartment.
Make sure the battery polarity is not
reversed.
Make sure the batteries are not dead.
If so, replace them with new batteries
031
Failure in communication with the zone 2 wireless
room thermostat.
032
Failure in communication with the zone 3 wireless
room thermostat.
033
Failure in communication with the zone 4 wireless
room thermostat.
034
Failure in communication with the zone 5 wireless
room thermostat.
035
Failure in communication with the zone 6 wireless
room thermostat.
036
Failure in communication with the wireless
outdoor sensor
The wireless outdoor sensor is too far
from the control unit.
Check the location of the outdoor sensor.
Check that the sensor’s power supply is
correctly provided by a photovoltaic cell.
15.2.2
Boiler fault codes
• Consult the boiler installation manual for information about
the fault codes.
15.2.3
Heat pump fault codes
• Consult the heat pump installation manual for information
about the fault codes.
15.3 Status
15.3.1 Boiler
status
• Consult the boiler installation manual for information about
the status codes.
15.3.2
Heat pump status
• Consult the heat pump installation manual for information
about the status codes.