Installation – Glow-worm Clearly Hybrid - Compact System User Manual
Page 22
0020096883_01 - 06/10 - Glow-worm
- 20 -
INSTALLATION
The automatic test will start.
The results appear in seconds,
indicating the status of each
component.
- If the connection is correct, the
message "OK" appears opposite the
component.
- If the connection is not correct, the
message "Not OK" appears opposite
the component.
In this case, check the connections.
12.7 Settings
This menu allows you to adjust different functions in accordance
with the connected appliances and to reset all the parameters.
• Using the buttons
,
select Settings on the screen.
• Press the buttony
to confi rm.
12.7.1 Heating
b
The maximum heating output temperature must be
adjusted in accordance with the characteristics of
your installation.
• Using the buttons
,
select Heating on the screen.
• Press the button
to confi rm.
This menu allows you to adjust the
installation’s maximum heating output
temperature (value adjustable between
30 ° C and 80 ° C - factory setting:
73°C).
• Press the button
.
• Press the button
.
• Increase or decrease with the
buttons
to display the
desired value.
• Press the button
to confi rm.
• Press the button
.
This menu allows you to select the
heating curve (value adjustable
between 0.2 and 4 - factory setting:
1.2), which allows you to obtain the
maximum heating demand for the usual
minimum outdoor temperature for the
region in which the sensor is installed.
• Using the buttons
,
select Heating curve adjustment on
the screen.
• Press the button
twice.
• Increase or decrease with the
buttons
to display the
desired value(s).
• Press the button
to confi rm.
b
Ensure that the heating curve setting is
compatible with the installation.
Heating curve
A
B
1
2
3
Key
1
Older properties with radiators
2
Standard/modern house with radiators
3
Highly insulated modern house with low temperature radiators
or underfl oor heating
A Heating
fl ow temperature (°C)
B External
temperature
• Press the button
twice.