Installation, 3 system connection, 4 connection of the 2 port valve – Glow-worm Clearly Hybrid - Compact System User Manual
Page 16
0020096883_01 - 06/10 - Glow-worm
- 14 -
INSTALLATION
6.5.3 System
connection
• Refer to the table below for the wiring of the systempro.
- Diagram 9 (9.1) : HYBRID COMPACT with 1 low heating
temperature zone (< 40°C) or 1 high heating temperature
zone (< 80°C)
Key
Description
Cable min.
230V~
Control unit electrical supply
3 x 0.75 mm²
REL1
Pump of the hydraulic module
3 x 0.75 mm²
REL2
DHW cylinder 2 port valve (*)
3 x 0.75 mm²
REL5
Heating circuit 2 port valve
2 x 0.75 mm²
IN1
DHW cylinder thermostat (*)
2 x 0.75 mm²
NTC1
Heating fl ow thermistor of the hydraulic
module
2 x 0.34 mm²
NTC2
DHW cylinder thermistor (*)
2 x 0.75 mm²
EBUS
EBUS connection of the heat pump
2 x 0.75 mm²
EBUS
EBUS connection of the boiler (respect the
polarity +/-)
2 x 0.75 mm²
(*) Not applicable for combi installations
- Diagram 9 (9.2) : HYBRID COMPACT with 2 low heating
temperature zone (< 40°C) or 2 high heating temperature
zone (< 80°C)
Key
Description
Cable min.
230V~
Control unit electrical supply
3 x 0.75 mm²
REL1
Pump of the hydraulic module
3 x 0.75 mm²
REL2
DHW cylinder 2 port valve (*)
3 x 0.75 mm²
REL4
Heating circuit 2 port valve "area 2"
2 x 0.75 mm²
REL5
Heating circuit 2 port valve "area 1"
2 x 0.75 mm²
IN1
DHW cylinder thermostat (*)
2 x 0.75 mm²
NTC1
Heating fl ow thermistor of the hydraulic
module
2 x 0.34 mm²
NTC2
DHW cylinder thermistor (*)
2 x 0.75 mm²
EBUS
EBUS connection of the heat pump
2 x 0.75 mm²
EBUS
EBUS connection of the boiler (respect the
polarity +/-)
2 x 0.75 mm²
(*) Not applicable for combi installations
- Diagram 9 (9.3) : HYBRID COMPACT with 3 low heating
temperature zone (< 40°C) or 3 high heating temperature
zone (< 80°C)
Key
Description
Cable min.
230V~
Control unit electrical supply
3 x 0.75 mm²
REL1
Pump of the hydraulic module
3 x 0.75 mm²
REL2
DHW cylinder 2 port valve (*)
3 x 0.75 mm²
REL3
Heating circuit 2 port valve "area 3"
2 x 0.75 mm²
REL4
Heating circuit 2 port valve "area 2"
2 x 0.75 mm²
REL5
Heating circuit 2 port valve "area 1"
2 x 0.75 mm²
IN1
DHW cylinder thermostat (*)
2 x 0.75 mm²
NTC1
Heating fl ow thermistor of the hydraulic
module
2 x 0.34 mm²
NTC2
DHW cylinder thermistor (*)
2 x 0.75 mm²
EBUS
EBUS connection of the heat pump
2 x 0.75 mm²
EBUS
EBUS connection of the boiler (respect the
polarity +/-)
2 x 0.75 mm²
(*) Not applicable for combi installations
6.5.4
Connection of the 2 port valve
1
3
L
N
230V~
1
3
L
N
REL1
1
3
L
N
REL2
1
3
L
N
REL3
1
2
L
N
REL4
1
2
L
N
REL5
1
2
L
N
IN1
When the 2 port valve is connected to REL3:
• Connect the neutral wire (blue) of the valve to the “N” of the
REL3 connector.
• Connect the live wire (brown) of the valve to the “L” of the
REL3 connector.
• Connect the earth wire (yellow/green) of the valve to the
earth of the REL3 connector.
• Electrically insulate the red and grey wires of the valve as
they are not used.
When the 2 port valve is connected to REL4 or 5:
• Connect the neutral wire (blue) of the valve to the “N” and
the live wire (brown) of the valve to the “L” of the REL4 or 5
connector.
• Connect the earth wire (yellow/green) of the valve to the
earth of the REL3 connector.
• Electrically insulate the red and grey wires of the valve as
they are not used.