3.0 Installation of the EX-6120, 6165 S

ERIES

IR

C

AUTION

:

Area must be declassified during installation.

The

EX-6120, 6165 S

ERIES

IR

gas sensor/transmitter (S/T) is a 3-wire, 24

V

DC

4-20 mA S/T for the detection of

combustible gas. The S/T is meant to be used in conjunction with an appropriate power supply and controller. The

EX-

6120, 6165 S

ERIES

IR

sensor/transmitter is in an enclosure rated for use in area listed below:

Certificate Numbers

IECEx SIR08.0009X,Code EX d IIC
SIRA 08atex1031x, Code EX d IIC

Standards

IEC 60079-0 : 2004 (Edition 4)
EN 60079-0 : 2006
IEC 60079-1 : 2007-4 (Edition 6)
EN 60079-1 : 2007

Temperature Codes

T4 (Ta-20 to +60 deg C)

Zones

1 & 2

Equivalent Rating

Class I, Division 1, Group A, B, D & D

Appropriate wiring, conduit and fittings are required for proper installation in an explosion proof rated environment.

C

AUTION

:

Since the sensor/transmitter detects gas only at the sensor location, pay attention to the possible sources of gas,

the density of the gas, locations where the gas may be confined and locations where the gas may damage or
injure property or personnel, when choosing locations of sensor/transmitters.

Take into consideration environmental factors when deciding on S/T location. Avoid locations where the S/T may be
damaged by liquid immersion, excessive heat or other known hazards. Also, take precautions to insure condensation
inside of the conduit does not enter the S/T.

3.1 Mounting the EX-6120, 6165 S

ERIES

IR Enclosure

Mount the enclosure, using the two mounting holes provided see Figure 2. Pay particular attention to the source and
density of the gas being detected when choosing the location. Mount the S/T near the ceiling for lighter than air gases
/vapors and near the floor for heavier then air gas/vapors. Contact

ENMET

if you have questions regarding your

application.

C

AUTION

:

Before connecting S/T to controller remove the power source to controller. Failure to do so may cause damage

to sensitive components.

Figure 2: EX-6120, 6165 S

ERIES

IR Mounting

Approximate Measurements in Inches (mm)

Maximum Depth = 5 Inches (127mm)

Optional
Conduit fitting
Typically: 3/4

NPT female

4.96 (126) Centers

4.53 (115)

9

.8

4

(

2

5

0

)

7

.4

8

(

1

9

0

)

2 x 0.27 (2 x 7) dia.

Mounting Holes

Optional Weatherguard

Inlet/Outlet

Port 1 of 2

Display

Menu Switches

Power & Alarm LEDs

Inlet/Outlet
Port 1 of 2

MENU UP DOWN ENTER