EX-6120, 6165 SERIES IR

ENMET Corporation

13

7 Fuses

A 1Amp anti-surge fuse, housed within a surface mounted holder, is located within the

EX-6120, 6165 S

ERIES

IR

to prevent

overloading of the electronic circuitry in the event of an internal fault.

In the event of the internal fuse blowing, access can be gained using the following procedure:

1.

Switch OFF the supply to the

EX-6120, 6165 S

ERIES

IR

.

2.

Release the grub screw located near the lip of the enclosure cover.

N

OTE

: It is not necessary to remove the grub screw to release the enclosure front cover.

3.

Remove the enclosure front cover by rotating it several times in a counter-clockwise direction.

4.

Unplug the display board from within the enclosure.

5.

Remove the 3 screws located around the edge of the next board.

6.

Unplug this board.

7.

The surface mounted fuse holder can now be located on the board below. Replace only with a fuse of the same type and
rating:-
1Amp Anti-surge ‘Nano fuse’

Assembly is the reverse of the above procedure.

8 Specifications

Materials

:

Instrument Body – Aluminium Pressure Die Casting
Sensor Housing – Stainless Steel Grade 303
Weather guard – Stainless Steel Grade 304 & Nylon 66

Cable entries

:

2 x 20 mm, or
2 x ½ NPT, or
2 x ¼ NPT

Weights

:

EX-6120, 6165 S

ERIES

IR (excluding weather guard) – 2.0 Kg ( 3.3 lb)

Magnetic Pen – 60 grams
Weather guard – 200 grams

Gas type

: Infrared – (Note: IR Sensors have not response to Hydrogen)

Input voltage

: 8 to 24 volts dc

Input power

: 5 Watts maximum

Internal fuse

: 1 Amp antisurge 'Nanofuse'

Analogue
output

:

4 to 20mA (10 bit resolution)

Relays

Relay 1 – Alarm 1
Relay 2 – Alarm 2
Relay 3 – Fault
Contact Rating 300Vac, 3 Amps (Non-inductive load)

RS232 output

: Communications with PC at 19200 baud

Sensor type

: NDIR Infrared

Measurement
range

:

Hydrocarbon Sensor (Methane Calibration)
0 – 100% LEL (5% vol. CH

4

) or 0 – 100% volume CH

4

Carbon Dioxide Sensor
Ranges form 0-1000ppm up to 0-100% Volume CO

2

Response time : Typically T

90

< 30 seconds (CH

4

)

Measurement
resolution

: 1% LEL or 1% volume (CH

4

)

IP rating

: Enclosure IP66, Sensor IP65

Display

: 4 Digit, 7 segment liquid crystal

Keypad

: 4-Button magnetically operated

Software

: Software configuration provided via LCD display and multifunction keypad

Operating
temperature

: - 20 to +60

O

C

Humidity range : 0 to 95% RH non-condensing
Operating
pressure

: Atmospheric + or - 10%

Performance
standards

: EN 60079-29-1:2007