ENMET EX-6165 User Manual

Page 20

background image

EX-6120, 6165 SERIES IR

ENMET Corporation

17

11.2.11 E : 13 – Relay 1

The unit is fitted with a relay that is operated in conjunction with the alarm level. The user can select if the relay is normally
Energized, E’ or normally de-energized, ‘d’ when the unit is not in an alarm condition.

From the menu system select menu option: E: 13 and press ENTER.

The display will show the following:

E:r

Normally energized, rising alarm

d:r

Normally de-energized, rising alarm

E:F

Normally energized, falling alarm

d:F

Normally de-energized, falling alarm

The mode of operation can be changed by pressing the UP button.

Press ENTER to accept the new relay mode of operation.
N

OTE

: Pressing MENU instead of ENTER leaves the unit without change.

Press MENU to return the instrument to its standard mode of operation.

11.2.12 E : 14 – Relay 2

The unit is fitted with a relay that is operated in conjunction with the alarm level. The user can select if the relay is
normally Energized, ‘E’ or normally de-energized, ‘d’ when the unit is not in an alarm condition.

From the menu system select menu option: E: 14 and press ENTER.

The display will show the following:

E:r

Normally energized, rising alarm

d:r

Normally de-energized, rising alarm

E:F

Normally energized, falling alarm

d:F

Normally de-energized, falling alarm

The mode of operation can be changed by pressing the UP button.

Press ENTER to accept the new relay mode of operation.
N

OTE

: Pressing MENU instead of ENTER leaves the unit without change.

Press MENU to return the instrument to its standard mode of operation.

11.2.13 E : 15 – Alarm Level 1

The gas level that will cause Relay 1 to change state is set via this menu option.

From the menu system select menu option: E: 15 and press ENTER.

Using the UP and DOWN buttons, adjust the displayed reading so that it matches the desired alarm set point.

Press ENTER to accept the new alarm level.
N

OTE

: Pressing MENU instead of ENTER aborts the feature.

Press MENU to return the instrument to its standard mode of operation.

11.2.14 E : 16 – Alarm Level 2

The gas level that will cause Relay 2 to change state is set via this menu option.

From the menu system select menu option: E: 16 and press ENTER.

Using the UP and DOWN buttons, adjust the displayed reading so that it matches the desired alarm set point.

Press ENTER to accept the new alarm level.
N

OTE

: Pressing MENU instead of ENTER aborts the feature.

Press MENU to return the instrument to its standard mode of operation.

11.2.15 E : 19 – Positive Zero Suppression

This option is used to allow the user to suppress small amounts of positive sensor zero drift. The setting can be set between 0 and 10%
of the sensor range as set by the FSD value.

Press MENU to open the menu system.

Using the NEXT and PREVIOUS buttons, select menu option: E:19

Press ENTER.

Using the INCREASE and DECREASE buttons, set the required zero suppression value.

Press ENTER to store the new value.
Note: Pressing the MENU button rather than the ENTER button exits without any change.

Press MENU to close the menu system.