3.8 Initial Gas Testing

EX-6120, 6165 S

ERIES

IR

units are factory calibrated as detailed on the calibration certificate supplied with the

instrument. However, it is always advisable after installation to confirm that the instrument reads zero with no gas
present and responds accurately when presented with an appropriate concentration of the target gas.

The

EX-6120, 6165 S

ERIES

IR

display becomes operational within 60 seconds however; the sensor should be allowed

to stabilize for the period of five to ten minutes before attempting to check the zero setting and gas response.

Refer to Figure 9 showing the arrangement for applying the test gas to the

EX-6120, 6165 S

ERIES

IR

.

1.

Before application of the test gas, check that the

EX-6120, 6165 S

ERIES

IR

reads zero with no known gas

present in the atmosphere. If necessary, carry out adjustment of the zero setting as described in section 5.1.1

2.

Apply the test gas and allow a sufficient time for the sample to reach the gas detector and for the sensor
response to stabilize.

Carrying out the above procedure, and comparing the results with previous readings, reference the certificate of
calibration, will confirm that the

EX-6120, 6165 S

ERIES

IR

is functioning correctly, both physically and electrically.

There is therefore no requirement for any further maintenance other than to clean the display window as required.

In the unlikely event that the response has changed from the previous readings, recalibrate the unit. See Section 5.1.1
and 5.1.2.

Figure 9: Appling Test Gas to EX-6120, 6165 S

ERIES

IR

3.8.1 Suggested calibration Test gas levels.

Hydrocarbon sensor:

Zero

contaminant free air.

Span

50% of the target gas(for 0 – 100% LEL range).

Carbon Dioxide sensor:

Zero

Nitrogen.

Span

Approximately 50% of Range.

With Weatherguard

Certified Test Gas
Cylinder

Sampling Tube

Flow Regulator

Calibration Adaptor with Weatherguard,
part number 04546-012

Calibration Adapter,

part number 03700-058