Setup parameters, Parameter tables, Etup – Bonaire Touchpad Control (LV) - Tekelek User Manual
Page 20: Arameters, Arameter, Ables, Setup & commissioning

Touch Pad Control
Setup & Commissioning
TEK600 Series Control
Page 20
Setup Parameters
There are a series of available parameters that can be modified to tailor the control to meet the customer’s requirements.
Carefully read these tables before entering the maintenance modes.
There are a number of potential product classes that the touch
pad control system will control. The class is the first
requirement for selection when entering the maintenance
mode.
Parameter Tables
Water Management
Installer Maintenance
Parameter
Default
OFF Value
ON Value
Dump Delay after shutdown
1
01
00 = OFF
01= 1 hr
Pre-Cool
2
01
00 = OFF
01 = 1.5 min
Dump Interval
3
00
00 = OFF
01,02,03,04,05,06 =
1, 2, 4, 8, 12,24 hrs
Sump fill before Pre-fill
4
01
00= OFF
01 = 1.5 min
Appliance Class
Code
Touch Pad Wall Control
tP
Heater
H
Evaporative A/C
E
Refrigerative A/C
C
Combined Heater - Cooler
HC
Diagnostic Mode
Installer
Maintenance
Parameter
Fill Valve
1
Fill Valve & Pump
2
Fan Speed
Installer
Maintenance
Parameter
Default
Value
Range
Low Fan Speed
1
92
40 – FF
High Fan Speed
2
FF
FF – 9b