Introduction
Your ducted evaporative air conditioner is engineered to meet the rigours of our harsh Australian environment.
Operated and maintained in accordance with this manual, it will provide you with years of quiet, cool and
environmentally friendly operation. Please take the time to read this manual.
The principal of your unit is to introduce fresh air, which is washed through the filter pads to provided cool fresh air.
The air is exhausted taking with it any heat loadings on the home.
Unit Operation
Exhaust
It is essential for successful operation of evaporative air-conditioning that there be sufficient exhaust openings in
the area to be ventilated. Open doors and windows will usually provide this.
The minimum exhaust opening should be as per the table guide set out below. It is recommended that ceiling
vents or exhaust fans be used where there is any doubt about there being sufficient exhaust area available.
Ceiling exhaust fans or ceiling vents should have a capacity equivalent to that of the air conditioner.
MODEL
MINIMUM EXHAUST
AREA
Small
0.85 m²
Medium
1.48 m²
Large
2.02 m²