beautypg.com

Austin Hughes Fan Unit & ICM-02 User Manual

Page 52

background image

www.austin-hughes.com

UM-ICM-02-Q215V1

P.47

Replacement, removal or addition for remote FAN unit

1.

How to replace the failed Master IP fan unit with a new one ?

Step 1

- Prepare a new Master IP fan unit and set it to 1st level.

( Please refer to user manual < 2.5 > for the fan unit level setting )

Step 2

- Disable alarm email in page.

Step 3

- Power off & remove the failed Master IP fan unit from connection.

Step 4

- Install the new Master IP fan unit to the connection & power it on.

Step 5

- Click Start Connection in page for the relevant Master IP Group.

Step 6

- Confi gure the new Master IP fan unit in

& page

such as Rack, Position, Alarm Temp...

Step 7

- Enable alarm email in page.

2.

How to replace a failed certain level remote fan unit with a new one ?

Step 1

- Prepare a new remote fan unit and set the remote fan unit level accordingly.

( Please refer to user manual < 2.5 > for the fan unit level setting )

Step 2

- Prepare an appropriate length Cat. 5 / 6 cable.

Step 3

- Click Set maintenance in

page for the failed remote fan unit.

Step 4

- Use a Cat. 5 / 6 cable to bridge over the failed remote fan unit which will be replaced

to minimize log / data loss.

Step 5

- Power off & remove the failed remote fan unit from connection.

Step 6

- Install the new remote fan unit, cancel the cable-bridging and reconnect the remote fan

unit to the last and next one.

Step 7

- Power on the new remote fan unit.

Step 8

- Click Remove maintenance in

page for the new remote fan unit.

Step 9

- Confi gure the new remote fan unit in

& page

such as Rack, Position, Alarm Temp...

Ignore step 2 & 4 if the failed remote fan unit is in the last level.

< Part IX >

Troubleshooting