beautypg.com

Suggested steam coil piping arrangment – American Dryer Corp. AD-100 User Manual

Page 55

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

SUGGESTED STEAM COIL PIPING ARRANGMENT

FIG . 1

Care must be exercised when leveling steam dryers in final position. After level­

ing the dryer, check the downward pitch of the heat exchanger from front to rear

with a level. Likewise, check the downward pitch of the return condensate manifold

toward its outlet port. Absence of these downward pitches will result in

probable water hammer and premature heat exchanger fracture and leakage.

The heat exchanger coils are designed to operate with dry steam only. The presence

of condensate in the steam will cause water hammer and subsequent heaL exchanger

failure. The steam supply connection must be taken from the top of a well dripped

steam main. If the supply run-out to the dryer exceeds twenty feet, it should be

dripped just before the control valve with a proper trap and a dirt pocket. (See

Figure 1)

Proper trap selection is mandatory. For low pressure units (15 psi or less) use

an F & T (float and thermostatic) trap. For pressures above 15 psi up to 125 psi

use bucket (inverted bucket) traps. DO NOT EXCEED 125 psi. Do not use thermo­

dynamic, disc, or impulse traps.

Condensate disposal is important. Do not elevate the condensate return line

after an F & T trap. Drain only by gravity into a properly-vented low pressure

return or condensate tank. A condensate line may be elevated after a bucket trap

only if there is sufficient pressure to overcome the head. Determine steam

pressure after deducting 12 psi for the control valve, coil, and trap losses.

(Each foot of elevation requires 1/2 pound of remaining pressure.)

Trap location is essential. The trap inlet should be positioned 12" minimum below

coil outlet to assure complete coil drainage.

10-7