Table 11 — 40QN Thermistor Properties*

TEMP

(F)

MINIMUM

OHMS

NOMINAL

OHMS

MAXIMUM

OHMS

MINIMUM

THERMISTOR

VOLTS — DC

NOMINAL

THERMISTOR

VOLTS — DC

MAXIMUM

THERMISTOR

VOLTS — DC

-40

303,300

342,700

386,200

4.80

4.82

4.84

-30

211,500

237,276

265,444

4.72

4.75

4.77

-20

149,721

166,689

185,146

4.61

4.65

4.68

-10

107,379

118,776

130,973

4.48

4.52

4.55

0

77,281

85,677

93,867

4.30

4.35

4.40

10

56,567

62,617

68,205

4.09

4.16

4.21

20

42,661

46,302

50,129

3.86

3.92

3.98

30

32,043

34,580

37,220

3.59

3.66

3.72

32

30,300

32,550

35,120

3.53

3,60

3.66

40

24,061

26,118

27,960

3.28

3.36

3.43

SO

18,650

19,900

21,180

2.99

3.05

3.11

60

14,402

15,312

16,219

2.67

2.73

2.79

70

11,247

11,883

12,518

2,36

2.42

2.47

80

8,820

9,299

9,779

2.06

2.11

2.16

90

6,846

7,339

7,754

1.76

1.83

1.88

100

5,487

5,829

6,187

1.52

1.57

1.63

110

4,367

4,667

4,976

1.29

1.34

1.40

120

3,502

3,760

4,026

1.09

1.14

1.19

130

2,830

3,051

3,281

0.92

0.97

1.02

140

2,300

2,489

2,687

0,77

0.82

0.87

150

1,880

2,045

2,216

0.65

0.69

0.74

160

1,547

1,688

1,836

0.55

0.59

0.63

170

1,280

1,402

1,531

0.46

0.50

0.53

180

1,065

1,170

1,282

0.39

0.42

0.45

190

890

982

1,078

0.33

0.36

0.39

200

748

828

913

0.28

0.31

0.33

210

631

701

766

0.24

0.26

0.28

212

611

678

751

0.23

0.25

0.28

'Circuit volts = 5 vdc.

Table

12

— Troubleshooting

PROBLEM

POTENTIAL SOURCE

ACTION

Unit does not
operate

Circuit breaker has tripped or fuse is blown

Reset the circuit breaker or replace the fuse.

Power failure

Restart fan coil unit operation when power is restored.

Voltage is too low

Confirm the available voltage.

Air filter is blocked with dust

Clean the air filter.

Temperature is not set properly

Check and reset if necessary.

Insufficient
Cooling

Window(s) and/or door(s) are open

Close window(s) and door(s).

Outdoor unit is obstructed

Remove the obstruction.

Fan speed is too low

Change the fan speed

Operation mode is set to fan or auto, mode

Change to cooling operation or reset temperature

(using remote controller).

Air filter is blocked with dust

Clean the air filter.

Insufficient

Temperature is not set properly

Check and reset if necessary.

Heating*

Window(s) and/or doorfs) are open

Close window(s) and door(s).

Outdoor unit is obstoicted

Remove the obstruction.

Unit stops

Off timer is operating

Turn off the off timer function.

during operation

Room temperature has reached the programmed set point

Normal unit operation.

'Heat pump systems only.