Step 6 — make piping connections – Carrier 38AN User Manual
Page 10
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

'2 1/2" TYP
□IA
Fig. 8 — Wall Hole Location For Fan Coil Unit
Rear Piping (Size 009 Shown)
WALL SLEEVE
(FACTORY SUPPLIED)
(INDOOR SIDE) • WALL . (OLTTDOOR SIDE)
NOTE: Slope condensate line at a minimum pitch of
V*
in. per foot.
Fig. 9 — Piping Hole
Step 5 — Connect Refrigerant Piping
— Refer
to Tables 4A-4D for correct piping sizes. The length of re
frigerant pipe depends on the unit placement and building
structure — run pipes as directly as possible. Piping lengths
must not exceed 35 ft of total run.
 CAUTION
DO NOT BURY MORE THAN 36 IN. OF REFRIG
ERANT PIPE IN THE GROUND. If any section of pipe
is buried, there must be a 6-in. vertical rise to the valve
connections on the outdoor unit. If more than the rec
ommended length is buried, refrigerant may migrate to
cooler, buried section during extended periods of unit
shutdown, causing refrigerant slugging and possible com
pressor damage at start-up.
If it has not yet been removed, remove indoor section front
panel by removing the Phillips head screws located at the
bottom of the air outlet. It may be necessary to rotate the
louvers to locate the mounting screws.
Make piping connections:
NOTE: Right rear piping connections are the preferred
configuration.
RIGHT REAR AND BOTTOM PIPING CONNECTIONS
1. Carefully separate the tubing and condensate drain tube
from the shipping brackets.
2. Be careful not to bend or kink the tubing. Gently rotate
the tubing 90 degrees.
3. Carefully position the indoor section onto the wall bracket.
Be sure the tubing and drain mbe are routed through the
piping hole in the wall.
4. Check that the indoor section is moxmted level to ensure
proper condensate drainage and to avoid possible water
damage. Be sure the drain tube is sloped toward the out
side and is not kinked or bent. Ensure that any drain ex
tension is made outside the wall.
RIGHT SIDE PIPING CONNECTIONS
1. Carefully remove the tubing and the condensate drain tube
from the shipping brackets.
2. Be careful not to bend or kink the tubing. Gently rotate
the tubing 180 degrees.
3. Using a hand tube bender, carefully bend the tube ends
until they coincide with the raceway opening.
4. Carefully position the indoor section onto the wall bracket.
Be sure the tubing and drain tube are routed through the
piping hole in the wall.
5. Check that the indoor section is mounted level to ensure
proper condensate drainage and to avoid possible water
damage. Be sure the drain tube is sloped toward the out
side and is not kinked or bent. Ensure that any drain ex
tension is made outside the wall.
LEFT SIDE PIPING CONNECTIONS
1. Place indoor unit on wall bracket.
2. Mark where the tube flare connection points end on the
wall.
3. Remove the indoor section from the wall bracket.
4. Route the interconnecting tubing and the drain tube ex
tension through the wall sleeve.
5. Using a hand tube bender, carefully bend the tubes until
they coincide with the position of the flare connection points
on the wall.
6. Secure indoor section to the wall bracket.
7. Connect the drain tube extension to the condensate drain
tube.
8. Carefully position the indoor section onto the wall bracket.
Be sure the tubing and the drain tube are routed through
the piping hole in the wall.
9. Check that the indoor section is mounted level, to ensure
proper condensate drainage and to avoid possible water
damage. Be sure the drain tube is sloped toward the out
side and is not kinked or bent. Ensure that any drain ex
tension is made outside the wall.
ALL TYPES PIPING CONNECTIONS
NOTE: After tubing is routed through wall sleeve, install the
factoiy-supplied w5l cap around tubing components and into
the 2Y2-in. hole. Do not fill air gaps yet with insulation or
caulking as this space is helpful when connecting tubing to
outdoor unit, and routing electrical power supply. Be sure to
fill air spaces after installation is complete.
IMPORTANT: All refrigerant lines must be insulated
because the refrigerant flow device is located in the
outdoor section.
Run liquid and suction refrigerant piping.
1. Run pipes as directly as possible, avoiding any unnec
essary turns and bends.
2. Suspend refrigerant pipes so that the insulation is not dam
aged and vibrations are not transmitted to the
structure,
3. Leave slack in refrigerant pipe between the structure and
the indoor and outdoor sections to absorb vibration.
Step 6 — Make Piping Connections
NOTE: The outdoor section must be connected to the indoor
section using field-supplied tubing.
To make coimections:
1. Unpack factory-supplied tubing package. Unwind tubing
carefully. Do not bend or kink tubing.
10