beautypg.com

Carrier 38AN User Manual

Page 11

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

2. Connect piping to the indoor section:

a. Shape tube with a tube bender so that the tube ends

coincide with flare connections.

b. Carefully remove the flare nut fitting from the indoor

section tubing.

c. Thoroughly clean all tubing connection points to pre­

vent foreign matter from entering the refrigerant
circuit.

d. Thread the 2 fittings by hand, making sure the threads

fit smoothly and the flare seats evenly against the union.

e. Tighten the 2 fittings securely. If a torque wrench is

used, hold the union side with a wrench and tighten
the nut to the specified torque with torque wrench.

See Table 6 for proper tightening torque.

Table 6 — Flare Nut Tightening Torque

FLARE NUT

TUBE

TORQUE

SIZE (in.)

DIAMETER (in.)

(ft-lb)

y*

V4

10-12

%

35-45

3. Connect piping to the outdoor section:

a. Carefully remove the flare nut from the service valves.

b. If necessary, shape the interconnecting tube with a tube

bender until the tube flare end coincides with the flare

connection on the service valves,

c. Carefully thread the flare nut onto the flare connection

point of the service valve.

d. Tighten the flare nut. See Table 6 for proper tighten­

ing torque.

4. Refrigerant line purge procedure:

a. Remove the service valve caps.
b. Use a hex key wrench to carefully rotate the valve stem

of the suction service valve 90 degrees (one-quarter
turn). Leave the valve open for approximately 5 sec­
onds, then return the valve to its closed position,

c. Purge refrigerant through the suction valve service port

for 5 seconds, following accepted refrigerant removal
procedure.

d. Rotate the valve stem of the liquid line service valve

^iproximately one-quarter turn counterclockwise. Leave
the valve open for approximately 3 seconds, then re­
turn the valve to its closed position.

e. Inspect the refrigerant line connections for leaks using

soapy water or electronic leak detector.

f.

If no leaks are found, open both valves. Reinstall ser­

vice valve caps.

g. Thoroughly reinspect all joints and connections for re­

frigerant leaks. Use soapy water or electronic leak de­

tector.

h. Tape both insulated tubing lines together. Begin tap­

ing from the bottom of the outdoor section to the point
where the tubing enters the wall. Do not tape too tightly

— this reduces the tubing insulation efficiency.

Step 7 — Connect Condensate Drain Line —

Observe all local sanitary codes when installing condensate
drains.

1. Connect drain lines by inserting a ys-in. ridged PVC pipe

over the drain connection fitting provided.

A

CAUTION

The drain tube extension must be securely fastened
to the condensate drain. Failure to do so can result
in condensate water dripping onto the floor.

IMPORTANT: Be sure the drain hose has no slack
which might form a trap.

Do not insert a trap in the

drain line, the drain is internally trapped.

3. Insulate the condensate drain line where it is located in or

above an oceupied area with a condensate-proof mate­
rial, such as polyurethane or neoprene.

Step 8 — Make Electrical Connections

— Be sure

all field wiring complies with local building codes and NEC,
and that the unit voltage is within the limits shown in
Table 7. For units with electric heat option, see Table 8.

Contact local power company for correction of improper

line voltage. Check the unit rating plate for recommended
circuit protection device.

A

WARNING

To avoid personal injury or damage to unit, do not make
electrical connections until all power sources are shut
down, locked out, and tagged off. Failure to do so could
result in personal injury or damage to unit.

A CAUTION

Operation of unit on improper line voltage constitutes

abuse and could affect warranty. Refer to Table 7 for
permissible operating limits. Do not install unit in sys­
tem where voltage may fluctuate above or below per­
missible limits.

NOTE: Use type NM (per NEC) power cable only (pro­

vided) between indoor disconnect switch (if installed) and
indoor unit.

NOTE: Install branch circuit disconnect per NEC of ad­

equate size to handle unit starting current. Locate diseonnect
within sight from and readily accessible from outdoor unit,
per Section 440-14 of NEC. Some codes allow indoor unit
to share disconnect with outdoor unit if disconnect can be
locked; check local code before installing in this manner.

A WARNING

According to NEC and most local codes, the unit must
have an uninterrupted, unbroken ground to minimize per­
sonal injury if an electric fault should occur. The ground

may consist of electrical wire or metal conduit when in­
stalled in accordance with existing electrical codes. Fail­
ure to follow this warning could result in an electric shock,

fire, or death.

A CAUTION

Do not short circuit the transformer — it is fused. The
transformer can be short circuited by connecting the wrong
wires or by touching a live wire to the side of a grounded
control box.

2. To ensure regular flow of condensate water, the drain pipe

should be pitched toward an open drain or sump at a down­

ward slope of at least Li-in. per ft. Refer to Fig. 10.

INDOOR SECTION WIRING

1. Remove fan coil unit front cover.

2. Route ground and power wires using NM wire provided.

Remove the factory test leads connected to the power ter­
minal block. These leads are for factory testing only and

cannot be used for power connections.

3. Route a 14-gage, 4-wire conductor (cooling only sys­

tems) or two 14-gage, 3-wire conductors (heat pump sys­
tems) through the power wiring hole in the control box.

NOTE: Connectors are factory supplied.

11

This manual is related to the following products: