beautypg.com

Warning – Carrier 48XL User Manual

Page 10

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

3, Secure flue hood to flue panel by inserting a single screw on

the top and the bottom of the hood,

r (25

mm)

MiN.

Return Duct Cover

Supply Duct Cover

Fig. 8 - 48XL with Duct Covers On

Provide for Condensate Disposal

NOTE:

Ensure that condensate-water disposal methods comply

with local codes, restrictions, and practices.

The units dispose of condensate through a 3/4 -in. NPT female
fitting that exits on the compressor end of the unit. Condensate
water can be drained directly onto the roof in rooftop installations
(where permitted) or onto a gravel apron in ground level
installations. Install a field-supplied condensate trap at end of
condensate connection to ensure proper drainage. Make sure that
the outlet of the trap is at least f in, (23 mm) lower than the
drain-pan

condensate connection to prevent the

pan from

overflowing. Prime the trap with water. When using a gravel apron,
make sure it slopes away from the unit.

If the installation requires draining the condensate water away from
the unit, install a field-supplied 2-in. (3f mm) trap at the
condensate connection to ensure proper drainage. Condensate trap
is available as an accessory or is field-supplied. Make sure that the
outlet of the trap is at least f in, (23 mm) lower than the unit
drain-pan

condensate connection to prevent the

pan from

overflowing. Connect a drain trough using a minimum of
field-supplied 3/4 -in. PVC or field-supplied 3/4 -in. copper pipe
at outlet end of the 2 -in. (3f mm) trap (See Fig. 9). Do not
undersize the tube. Pitch the drain trough downward at a slope of at
least f in, for every fO ft. (3 m) of horizontal run. Be sure to check
the drain trough for leaks. Prime the trap at the beginning of the
cooling season start-up.

Install Flue Hood

^ WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal
injury or death.

The venting system is designed to ensure proper venting.
The flue hood assembly must be installed as indicated in
this section of the unit installation instructions.

Install the flue hood as follows:

f. This installation must conform with local building codes

and with the National Fuel Gas Code (NFGC), NFPA
34/ANSI Z223.f (in Canada, CAN/CSA Bf49.f, and
Bf49.2) or latest revision. Refer to provincial and local
plumbing or wastewater codes and other applicable local
codes,

2, Remove flue hood from shipping location (inside the return

section of the blower compartment-See Fig. 8). Remove the
return duct cover to locate the flue hood. Remove two
screws on flue panel. Place flue hood assembly over flue
panel. Orient screw holes in flue hood with holes in the flue
panel.

Install Gas Piping

The gas supply pipe enters the unit through the access hole
provided. The gas connection to the unit is made to the f/2-in,
FPT gas inlet on the gas valve.

Install a gas supply line that runs to the heating section. Refer to
Table 2 and the current edition of NFGC in the U.S, and the current
NSCNGPIC in Canada. Do not use cast-iron pipe. It is
recommended that a black iron pipe is used. Check the local utility
for recommendations concerning existing lines. Size gas supply
piping for 0.3 IN. W.C, maximum pressure drop. Never use pipe
smaller than the f/2-in. FPT gas inlet on the unit gas valve.

For natural gas applications, the gas pressure at unit gas connection
must not be less than 4,0 IN, W.C, or greater than 13 IN, W.C,
while the unit is operating. For propane applications, refer to
propane conversion kit instructions.

A 1/8-in, NPT plugged tapping, accessible for test gauge
connection, must be installed immediately upstream of the gas
supply connection to the gas valve and downstream of manual
equipment shutoff valve.

When installing the gas supply line, observe local codes pertaining
to gas pipe installations. Refer to the NFPA 34/ANSI Z223,1-2006
(in Canada, CAN/CSA B149.1).

NOTE: In the state of Massachusetts:

1, Gas supply connections MUST be performed by a licensed

plumber or gas fitter.

2, When flexible connectors are used, the maximum length

shall not exceed 36 in. (913 mm).

3, When lever handle type manual equipment shutoff valves

are used, they shall be T-handle valves.

4, The use of copper tubing for gas piping is NOT approved

by the state of Massachusetts,

In the absence of local building codes, adhere to the following
pertinent recommendations:

1, Avoid low spots in long runs of pipe. Grade all pipe 1/4 in,

(6.33 mm) for every 13 ft (4,6 m) of length to prevent traps.
Grade all horizontal runs downward to risers. Use risers to
connect to heating section and to meter.

2, Protect all segments of piping system against physical and

thermal damage. Support all piping with appropriate straps,
hangers, etc. Use a minimum of one hanger every 6 ft. (1,8
m).

For

pipe

sizes

larger

than

1/2

in,,

follow

recommendations of national codes,

3, Apply joint compound (pipe dope) sparingly and only to

male threads of joint when making pipe connections. Use
only pipe dope that is resistant to action of liquefied
petroleum gases as specified by local and/or national codes.
Never use Teflon tape,

4, Install sediment trap in riser leading to heating section (See

Fig. 10). This drip leg functions as a trap for dirt and
condensate,

3, Install an accessible, external, manual main shutoff valve in

gas supply pipe within 6 ft (1,8 m) of heating section.

6, Install ground-joint union close to heating section between

unit manual shutoff and external manual main shut off
valve.

10