Fig. 2 — line power connections – Carrier 38SE User Manual
Page 4
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Table 4 — Electrical Data
COND
UNIT
V/PH
OPER
VOLTS*
COMPR
FAN
BRANCH CIRCUIT
LRA
FLA
FLA
Wire
Sizet
(AWG)
Max
Ftt
Wire
Fuse
Ampst
Max
Min
38GR002---
72.0
14.8
1.0
12
32.0
30
38GR0023I0
72.0
14.8
1 0
12
1. '
32 0
30
38GR003---
90.0
19.2
1.1
10
39 0
40
38GR003310
90.0
19.2
1.1
10
39.0 L
40
38GR004---
230/1
253
207
100.0
22.9
1 3
10
33.0
50
38GR0043J0
100 0
22 9
1 3
10
33-0
50
38GR045---
94.0
23.9
1.3
8
49.0
50
38GR005---
106.0
27.9
2.0
8
42 0
Í
60
38GR006---
135.0
39.0
2.0
6
47.0
80
38GR003---
60.0
13.0
1.1
12
42.0
30
38GR0034Н0
70.0
13.0
1 1
12
М
42.0
30
38GR004---
69.0
14 0
1.3
12
39.0
30
38GR0044J0
200/3
220
180
80 0
14 0
1.3
12
1.'^ zL.
39.0 i: '
30
38GR045---
79.0
16.7
1.3
12
Í
33 0 i
35
38GR005---
87.0
18.3
2.0
10
r
46.0
40
38GR006---
113.0
24.0
2 0
8
64.0 /
50
38GR003---
50.0
11.5
1 1
12
25
38GR0035Í0
60.0
11.5
1 1
12
mf.
52.0 1
25
38GR004---
60.0
12.6
1.3
12
47.0
25
38GR0045J0
230/3
253
207
70.0
12.6
1 3
12
47.0
25
38GR045---
67.0
14 3
1 3
12
42 0
30
38GR005---
70.0
16.4
2 0
10
56.0
35
38GR006---
98.0
19.9
2 0
10
47 0
45
38GR004---
30.0
6.5
5
14
\ - x i :
110.0
15
38GR004610
35.0
6.5
5
14
110.0
15
38GR045---
460/3
506
414
35 0
7.2
.5
14
i
n
;
100.0 1
15
38GR005---
35.0
8 8
1.3
14
1
n
81.0
Í
20
38GR006---
49.0
10 4
1.3
14
70.{'
20
38SE002--.
65.0
10.3
.8
14
2 9 1
'■
20
38SE003---
72.0
14.8
.8
12
10
32 0
$ X Ù
30
38SE004---
230/1
253
207
90.0
19 2
.8
10
40.0
40
38SE045---
94.0
23 9
1 3
10
»
32 0
SBJB
50
38SE055---
L__
106.0
28.0
2.2
10
430
60
Corresponding wire sizes and wire lengths
FLA — Full Load Amps
LRA — Locked Rotor Amps
--------Electrical data shown applicable to all units for which com
plete model numbers are not shown Example: 38GR003---
applies to all 003 models except 38GR003Ji0.
*Permissible limits of the voltage range at which the unit will oper
ate satisfactorily
tCopper wire sizes and lengths Use latest National Electrical Code
(NEC) for aluminum wire sizing
-> Maximum dual element fuse size
NOTE Control circuit voltage is 24 volts on all units On 3-phase
units, phases must be balanced within 2%
3-PHASE
CONN.TO
FUSED
DISCONNECT
I-PHASE
CONN TO
FUSED
DISCONNECT
— GROUND LEAD-
GROUNDING LUG
- -----------------BRN _
L
■ --------------- ORN-----------
—
-------- BLK-----------
(38GR ONLY)
COND UNIT
A—A Splice Connections
--------- Field Wiring
--------- Factory Wiring
Fig. 2 — Line Power Connections
Install a Branch Circuit Fused Disconnect
of adequate size
to handle unit starting current Locate disconnect within
sight of and readily accessible to the unit, per section
440-14 of National Electrical Code (NEC).
Bring Line Power Leads Into Unit
— Extend leads from
fused disconnect thru hole provided in base pan (Fig. 1)
and into unit junction box.
CONNECT GROUND LEAD TO GROUND LUG OR
SCREW IN JUNCTION BOX for safety. Connect power
wiring. See Fig. 2. Splice line power leads to brown and
orange pigtails on 1-phase units or brown, orange and black
pigtails on 3-phase units. Use wire nuts supplied with unit.
Tape each connection. When aluminum field wire is used,
lubricate splices with splice compound (also supplied)
before using wire nuts.
Control Power
(24 v) wiring is brought thru hole provided
in unit base pan (Fig. 1) and into low-voltage section of
unit junction box. Splice control leads to yellow pigtails on
control relay. See Fig. 3. For aluminum wire splices use
factory supplied and lubricated wire nuts. Furnace or fan
coil transformer must be used as 24-v supply for system as
shown in Fig. 3. All 38SE units are equipped with
transformer used to power contactor thru unit control
circuit only, and must not be used to power thermostat
circuit.
1076