3. For all applications, the horizontal length of vent and

vent connector must not exceed the vertical height of
the vent system.

4. Addition of insulation to vent connector and vent

allows for longer horizontal runs in certain applications
as indicated with an asterisk (*) in appropriate tables.

5. When Type B-1 vent pipe is used for vent connector, it

must be insulated as indicated with an asterisk (*) in
the vent tables.

Table 8—Dedicated Type B-1 Vent For

58PAV075-GC and JC Maximum

Horizontal Length Allowed (Ft)

A89017

Fig. 11 —Dedicated Vent (Typical)

Table 6—Dedicated Type B-1 Vent For

58PAV035-EC and GC Maximum

Horizontal Length Allowed (Ft)

Height

Number of 90° Elbows

Vent

Pipe

0

1

2

3

4

5

5

0

5

5

4

NA

NA

4-lN.

DIAMETER

10

0

10

10

10

10

10

15

0

10

10

10

10

10

20

0

6

6

6

6

6

20*

0

20*

20*

20*

20*

20*

25

0

NA

NA

2

2

2

25*

0

25*

25*

25*

25*

25*

30

NA

NA

NA

NA

NA

NA

30*

0

30*

30*

30*

30*

30*

5

0

5

5

5

5

5

5-IN.

DIAMETER

10

0

4

4

4

4

4

15

0

NA

NA

NA

NA

NA

15*

0

15*

15*

15*

15*

15*

20

NA

NA

NA

NA

NA

NA

20*

0

20*

20*

20*

20*

20*

25

NA

NA

NA

NA

NA

NA

25*

0

25*

25*

25*

25*

25*

30

NA

NA

NA

NA

NA

NA

30*

0

30*

30*

30*

30*

30*

Height

Number of 90° Elbows

Vent

Pipe

0

1

2

3

4

5

5

NA

NA

NA

NA

NA

NA

4-IN.

DIAMETER

10

0

10

NA

NA

NA

NA

15

0

15

15

15

NA

NA

20

0

20

20

20

16

10

25

0

25

25

25

25

20

30

0

30

30

30

30

30

5

0

5

5

5

NA

NA

5-IN.

DIAMETER

10

0

10

10

10

10

10

15

0

15

15

15

15

15

20

0

20

20

20

20

20

25

0

22

22

22

22

22

30

0

20

20

20

20

20

NA—Not allowed. Condensation or positive pressure In vent system

could occur.
♦Insulated with 1-in. of foil-backed Insulation per Section A.5.

Table 9—Dedicated Type B-1 Vent For

58PAV090-GC, JC, and LC Maximum

Horizontal Length Allowed (Ft)

Table 7—Dedicated Type B-1 Vent For

58PAV055-EC and GC Maximum

Horizontal Length Allowed (Ft)

Height

Number of 90° Elbows

Vent

Pipe

0

1

2

3

4

5

5

NA

NA

NA

NA

NA

NA

4-IN.

DIAMETER

10

NA

10

NA

NA

NA

NA

15

0

15

8

6

NA

NA

20

0

20

20

16

12

4

25

0

25

25

24

18

12

30

0

30

30

30

28

22

5

0

5

2

NA

NA

NA

5-IN.

DIAMETER

10

0

10

10

10

NA

NA

15

0

15

15

15

15

15

20

0

20

20

20

20

20

25

0

25

25

25

25

25

30

0

30

30

30

30

30

Height

Number of 90° Elbows

Vent

Pipe

0

1

2

3

4

5

5

0

5

NA

NA

NA

NA

4-IN.

DIAMETER

10

0

10

10

10

NA

NA

15

0

15

15

15

15

15

20

0

20

20

20

20

20

25

0

18

16

16

16

16

25*

0

25*.

25*

25*

25*

25*

30

0

14

14

14

14

14

30*

0

30*

30*

30*

30*

30*

5

0

5

5

5

NA

NA

5-IN.

DIAMETER

10

0

10

10

10

10

10

15

0

15

15

15

15

15

20

0

12

12

12

12

12

20*

0

20*

20*

20*

20*

20*

25

0

8

8

8

8

8

25*

0

25*

25*

25*

25*

25*

30

0

4

4

4

4

4

30*

0

30*

30*

30*

30*

30*

NA—Not allowed. Condensation or positive pressure In vent system

could occur.

Table 10—Dedicated Type B-1 Vent For

58PAV110-JC and LC Maximum Horizontal

Length Allowed (Ft)

NA—Not allowed. Condensation

could occur.
♦Insulated with 1-in.

or positive pressure in vent system

of foil-backed insulation per Section A.5.

Height

Number of 90° Elbows

Vent

Pipe

0

1

2

3

4

5

5

NA

NA

NA

NA

NA

NA

5-IN.

DIAMETER

10

0

10

6

NA

NA

NA

15

0

15

15

15

15

6

20

0

20

20

20

20

20

25

0

25

25

25

25

25

30

0

30

30

30

30

30

5

0

5

5

4

NA

NA

6-IN.

DIAMETER

10

0

10

10

10

10

10

15

0

15

15

15

15

15

20

0

20

20

20

20

20

25

0

25

25

25

25

25

30

0

30

30

30

30

30

NA—Not allowed. Condensation

could occur.

or positive pressure in vent system