beautypg.com

Table 4—electrical data – Carrier 38QE User Manual

Page 11

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Table 4—Electrical Data

VOLT/PHASE

OPERATING

VOLT AG £♦

COMPRESSOR

FAN

MAX FUSE or

HACRTYPE

CIRCUIT BKR

AMPS

INDOOR COMPRESSOR SECTION

MIN

MAX

LRA

RLA

FLA

MCA

38QE024300

208/230/1

187

254

35.0

20.3

40

25.9

38QE036300

208/230/1

187

254

35.0

25.3

50

32.4

OUTDOOR FAN-COIL SECTION
38QE924300

208/230/1

187

254

.5

38QE936300

208/230/1

187

254

.7

WATER HEATER CONTROL BOX
38QE9XX300

208/230/1

187

254

20

20

FLA —Full Load Amps
HACR—Heating, Air Conditioning and Refrigeration
MCA —Minimum Circuit Amps
RLA —Rated Load Amps
LRA —Locked Rotor Amps

♦Permissible limits of the voltage range at which the unit will operate

satisfactorily.

♦♦Outdoor Coil Wiring—For 25-ft wire run or less, use minimum 14 AWG

wire size. For longer wire run, use same size wire as supply to compres­
sor section.

230 V operation. The primary connection on control trans­
formers must be rewired to the 208 volt wires for line volt­
age between 187 emd 218 Volts. Refer to the 38QE Compres­
sor Section label wiring diagram for location and wire identi­

fication to rewire the two (2) transformers in the main con­
trol box. Refer to the 40QE label wiring diagram for loca­
tion and wire identification to rewire the transformer in the

accessory heater or cooling-only control package. Cap each

unused transformer wire with a wire nut and tape or, if the
unused lead has a push-on terminal, tape and protect any
exposed metal on the terminal.

Compressor Section

InstaR branch circuit disconnect of adequate size to handle

compressor section. Route line power leads from disconnect
through hole provided in compressor section top rear panel

and into the main control box. Connect ground wire to
ground lug. Connect main power to the terminal block

located within the main control box. The compressor section
wire label illustrates the terminal block location.

Rear panel wiring holes are shown in Fig. 4. See Fig. 12 for
connection schematic.

Outdoor Fan Coil Section

The outdoor fan coil section receives power from the com­
pressor section. Provide a separate disconnect switch for
the outdoor fan cofi. section. Fig. 12 illustrates the connec­
tions from the compressor section to the disconnect switch
and then to the outdoor fan coil section.

Connect ground wire to ground lug. Route power wires for
the outdoor fan coil section through the 7/8-in. hole provided

in the top rear panel of the compressor section. Splice wires

to pigtails with wire nuts.

Connect the power wires to the outdoor disconnect switch.
From the disconnect switch, extend wires through hole pro­

vided in outdoor fan coil section and into line voltage sec­
tion of control box. Splice leads to black and yeUow pigtails
with wire nuts. Connect ground wire to ground lug inside
control box.

Domestic Water Heater Control Box (Electric Heater Only)

Install branch circuit disconnect of adequate size to handle
domestic water heater. Fig. 13 illustrates the required wir­

ing connection between the branch disconnect and the 38QE

38QE Compressor
Section Control Box

Splice Connection

Field Wiring

Factory Wiring

Fig. 12—Compressor Section and Outdoor

Section Power Connections

11