beautypg.com

Notes for label wiring diagrams – Carrier 58GS User Manual

Page 3

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

CAUTION: Use copper or copper-dad aluiai-
num conductors only. Use a separate branch
electrical circuit for this furnace.

A disconnect­

ing means must be located within sight of, and
readily accessible to, the furnace.

See Fig. 2 for wiring diagram showing the proper

field high- and low-voltage wiring. Make all elec­
trical connections in accordance with the National

Electrical Code and any local codes or ordinances

that might apply.

WARNING: The unit cabinet m.ust have an

uninterrupted or unbroken electrical ground to

minimize personal injury if an electrical fanlt

should occur. This may consist of electrical
wire or approved conduit when installed in
accordance with e.Kisting electrical codes.

exposed to cold air infiltration, drafts from win­
dows, doors, or other openings leading to the out­

side, or exposure to air currents from warm or cold
air registers; or to exposure where the natural circu­
lation of the air is cut off — such as behind doors,

above or below mantels, shelves, etc.

The thermostat should not be exposed to heat

from nearby fireplaces, radios, televisions, lamps,

or rays from the sun. Nor should the thermostat be
mounted on a wall containing pipes or warm air
ducts, or a flue or vent that could affect its
operation and prevent it from properly controlling
the room temperature. Any hole in the plaster or
panel thru which the wires pass from the
thermostat should be adequately sealed with suit­
able material to prevent drafts from affecting the

thermostat.

LOW-VOLTAGE WIRING — Make field low-

voltage connections at the low-voltage terminal
strip. See Fig. 2.

Set the thermostat heat anticipator at the

settings indicated below. If additional controls are
connected in the thermostat circuit, their amp draw
must be added to this setting. Failure to make the
setting will result in improper operation of the
thermostat.

58GS050 thru 150 sizes with

BDP 646AW gas valve.
Heat/Cool or Heat only models................ 0.55 amp

58GS175 size with Essex 242NS gas valve,

Heat/Cool models.......................................0.65 amp

With addition of automatic vent damper, antici­
pator setting should be 0.12 amp.

The room thermostat should be located where it

will be in the natural circulating path of room air.
Avoid locations where the thermostat would be

NOTES FOR LABEL WIRING DIAGRAMS

1

Screw terminals for field wiring connections

1/4-in quick connect terminals

3

L"

If

J Heating fan relay contact is normally closed until

r "

1 1 5

vac is applied to furnace

4

To change motor speed, move black or red wire to desired speed

setting

5

If any of the original wire as supplied with the appliance must

be replaced, it must be replaced with AWM (105 C) wire or its
equivalent

6 Motor is thermally overload protected

7

Factory speed selection is tor average conditions See installa­

tion instructions for optimum speed selection Motor may be 3
or 4 speed

8 Symbols are an electrical representation only

FOUR WIRE-

©Cp

TWO WIRE HEATING ONLY

JL

Jl

©-■

■=r

&

&-

LOW-VOLTAGE
TERMINAL BLOCK

Field

Low-Voltage

Wiring

Field

High-Voltage

Wiring

Factory Low-Voltage Wiring

THERMOSTAT
TERMINALS

I TWO WIRE

CONDENSING

UNIT

.

q

^JZL

-CHMV

-Ijj^

— ———

= GN0

SINGLE
PHASE

NOTE: If any of the original wire as supplied, must be replaced,
use same type or equivalent wire

Fig. 2 — Heating and Cooljng Application Wiring Diagram