beautypg.com

Carrier 50DP User Manual

Page 7

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Table 3 — Electrical Data; 50DP014

VOLTS/PH/HZ

VOLTAGE

RANGE

COMPR

OUTDOOR

FAN MOTOR

INDOOR

FAN MOTOR

FACTORY INSTALLED

HEATERS

POWER SUPPLY

Min Ckt

Amps

Max Fuse

Amps

Min

Max

RLA

LRA

Qty

FLA

Hp

FLA

FLA

Nom Kw

2.0

7 4

__

80

90

3.0

8.4

80

90

2.0

7 4

39

18.8

80

90

2 0

7.4

72

34 2

100

LOO

200/3/60

180

220

27.0

160

2

4.6

2.0
2.0

7 4
7.4

117
156

56.1

74.8

160

205

150

200

3.0

8.4

39

18.8

80

■ ■■ ■ 90..

3.0

8.4

72

34.2

105

: 10

3.0

8.4

117

56 1

165

; 75

3 0

8.4

156

74 8

210

200

2.Ò

6.6

_

__

70

SO

3.0

8 4

-

-

70

8C'

2.0

6 6

47

18.8

70

:7L::::A8e.:A.;/

230/3/60

207

253

22.8

137

2

4 5

2 0
2 0

6.6
6.6

82

135

34 2
56 1

115
180

М М0 .

] 75

3 0

8.4

47

18.8

70

30 ■

3.0

8.4

82

34.2

120

DO

3.0

8.4

135

56.1

185

' / J

2 0

3.3

__

_

35

i 40

3.0

4.2

_

40

40

2.0

3 3

21

17.1

35

40

460/3/60

414

508

11.6

69

2

2.3

2.0
2 0

3.3
3.3

39
66

32.4
55 0

55
90

60

3 0

4 2

21

17.1

40

40

3.0

4.2

39

32.4

55

50

3.0

4.2

66

55 0

90

SO

575/3/60

518

632

9.3

55

2

1 8

2 0
3,0

2 3
3.8

-

-

30
30

30

Compr — Compressor

FLA — Full Load Amps
Hp — Horsepower

LRA — Locked Rotor Amps
RLA — Rated Load Amps

Fuse only; unshaded values indicate fuses or circuit

breakers

may be used

Table 4 — Electrical Data; 50DP016

VOLTS/PH/HZ

VOLTAGE

RANGE

COMPR

OUTDOOR

FAN MOTOR

INDOOR

FAN MOTOR

FACTORY INSTALLED

HEATERS

POWER SUPPLY*

Min

Max

RLA

LRA

Qty

FLA

Hp

FLA

FLA

Nom Kw

Min Ckt

Amps

Max Fuse

Amps

_

_

105

125

72-82

34.2

105-120

125

208-230/3/60

187

253

61.6

266

2

6.6

3

10.4

117-135

6.1

165-185

150-175

156-180

74.8

210-240

200-225

55

60

39

32.4

55

60

460/3/60

414

508

32

120

2

3.3

3

4.7

66

55.0

90

90

96

79.8

130

125

575/3/60

518

632

25.6

96

2

2.6

3

3 8

-

-

50

45

Compr

— Compressor

LRA

FLA

— Full Load Amps

RLA

Hp

— Horsepower

Locked Rotor Amps
Rated Load Amps

*Fuse only.

balanced within 10%. Contact local power com­
pany for correction of improper voltage or phase
imbalance. Unit failure as a result of operation on
improper line voltage or excessive phase imbalance

constitutes abuse and may cause damage to elec­
trical components. Such operation would invali­
date applicable Carrier warranty.

Field Control Wiring

— Install a Carrier-approved

accessory thermostat assembly according to instal­
lation instructions included with accessory. Locate
thermostat assembly on a solid wall in the condi­
tioned space to sense average temperature.

Route thermostat cable or equivalent single

leads of no. 18 AWG colored wire from subbase

terminals thru conduit in unit to low-voltage
connections as shown on unit label wiring diagram

and in Fig. 11. Use no. 16 AWG wire for lengths
exceeding 50 feet. Set heat anticipator settings as
indicated in Table 5. Settings may be changed
slightly to provide a greater degree of comfort for a
particular installation.

Refer to accessory remote control panel in­

structions as required.

Return Air Filters

— Check that correct filters are

installed in filter tracks. See Table 1. Do not

operate unit without return air filters.

Outdoor Air Inlet Screens

— Outdoor air inlet

screen(s) must be in place before operating unit.