beautypg.com

Table 1 — physical data – Carrier 50DP User Manual

Page 2

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Table 1 — Physical Data

UNIT SIZE 50DP

012

014

016

OPERATING WT (lb)

Unit

1350

1410

1590

With Economizer

1500

1560

1740

Roof Curb

200

200

200

COMPRESSOR

Hermetic -- 2 Cy t inders

Semi-Hermetic — 6 Cylinders

No. ... Type

2 ... P64

2 ... P77

1 . 06DA537

Oil (oz)

76 ea

76 ea

160

REFRIGERANT (Capillary Control)

R-22

R-22

R-22

Charge (lb) Sys 1*, Sys 2

7 9, 6.6

8 3, 8.3

23.2, -

OUTDOOR COIL

Copper Tube, Aluminum Plate Fins/in.

Rows

2

3

3

F ins/in.

14

14

14

Total Face Area (sq ft)

18.9

18 9

18 9

OUTDOOR AIR FAN

Prope 1 ler Type. Direct Drive

Nominal Cfm

9000

8000

12,000

No. ... Diam (in.)

2 ..22

2 22

2 ... 26

Motor Hp (1075 Rpm)

1/2

1/2

1

INDOOR COIL

Copper Tube, Aluminum Plate Fins/in

Rows

2

3

3

F ins/in.

14

15

14

Total Face Area (sq ft)

14.7

13.8

........................ _ .... . .............................................

16.5

INDOOR BLOWER

Centrifugal, Adjustable Belt Drive

Qty ... Size (in.)

2 .. 1 0 x 1 0

2 1 0 x 1 0

2 . . 1 0 X 1 0

Nominal Cfm

4000

5000

6000

Std

753-1066

805-1093

916-1 186

Rpm Range

878-1191

978-1265

1158-1428

Max Allowable Rpm

1550

1550

1550

Std

2 4-3.4

2 8-3.8

3.4-4.4

Motor Pulley Pitch Diam (in.)

2.8-3.8

3.4-4 4

4.3-5.3

Std

5.5

6.0

6.4

Fan Pulley Pitch Diam (in.)

5.5

6.0

6.4

Belt, No. ... Type ... Length (in.)

1 ... V .. 41

1 ... V . 43

1 . V ... 45

Speed Change per Full Turn Std

62

58

54

of Moveable Pulley Flange (Rpm) Opt

63

57

55

Moveable Pulley Max Full Turns

from Closed Position

Factory Setting - Full Turns Open

5

5

5

753

805

916

Factory Speed Setting (Rpm)

878

978

1158

Std

1 (1.25)

2 (1.15)

3 (1 15)

Motor Hp (Service Factor)

1-1/2 (1.20)

3 (1.15)

3 (1 15)

HIGH PRESSURE SWITCH

Cutout (psig)

428

Reset (psig)

320

LOW PRESSURE SWITCH (Liquid Line)

Cutout (psig)

27

Reset (psig)

60

AIR INLET SCREENS

2 ... 20x25x1

Economizer, No. ... Size (in.)

1 .. 20x20x1

INDOOR AIR FILTERS (Type)

10% efficient — 2-in. D

isposable Fiber Glass

2 ... 16x20x2

2 16x20x2

4 ... 20x20x2

No. ... Size (in.)

4 .. 16x25x2

4 ... 16x23x2

4 .. 16x20x2

t

•System 1 consists of upper portion of outdoor coil and lower portion of indoor coil