beautypg.com

A caution – Carrier 58TUA User Manual

Page 6

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

A89014

Fig. 6—Leveling Leg Installation

The gas supply line should be a separate line running directly from
the gas meter to the furnace, if possible. Refer to Table 4 for the
recommended gas pipe size. Risers must be used to connect to the
furnace and the meter.

A CAUTION

If a flexible connector is required or allowed by the authority
having jurisdiction, black iron pipe shall be installed at the
gas valve and extend a minimum of 2 in. outside the furnace
casing.

Table 4—Maximum Capacity of Pipe*

NOMINAL

IRON PIPE

SIZE (IN.)

INTERNAL

DIAMETER

(IN.)

LENGTH OF PIPE (FT)

10

20

30

40

50

1/2

0.622

175

120

97

82

73

3/4

0.824

360

250

200

170

151

1

1.049

680

465

375

320

285

1-1/4

1.380

1400

950

770

660

580

1-1/2

1.610

2100

1460

1180

990

900

* Cubic ft of gas per hr, for gas pressures of 0.5 psig (14-in. wc) or iess, and

a pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table
10-2, NFPA 54-1992.

Piping should be pressure-tested in accordance with local and
national plumbing and gas codes before the furnace has been
attached. If the test pressure exceeds 0.5 psig (14-in. wc), the gas
supply pipe must be disconnected from the furnace and capped
before the pressure test. If the test pressure is equal to or less than
0.5 psig (14-in. wc), close the manual shutoff valve located on the
gas valve before the test. It is recommended that the ground joint
union be loosened before pressure testing. After all connections
have been made, purge the lines and check for leakage with

regulated gas supply pressure.

Install a sediment trap in the riser leading to the furnace. The trap
can be installed by connecting a tee to the riser leading from the
furnace. Connect a capped nipple into the lower end of the tee. The

capped nipple should extend below the level of the gas controls.
(See Fig. 7.)

Canadian installations must be installed in accordance with
CAN/CGA-B149 Installation Codes, and all authorities having

jurisdiction.

Fig. 7—^Typical Gas Pipe Arrangement

Apply joint compound (pipe dope) sparingly and only to the male

threads of each joint. The compound must be resistant to the action
of propane gas.

Install an accessible manual shut-off valve upstream of the furnace
gas controls and within 72 in. of the furnace. A 1/8-in. NPT
plugged tapping, accessible for test gage connection, must be