A caution, Table 12-^gas rate cu ft/hr – Carrier 58TUA User Manual
Page 16
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
EXAMPLE:
Heat value 1040
Btu/cu ft specific gravity 0.62
Therefore; Orifice No. 45* with manifold pressure 3.7-in.
wc on high fire and 1.6-in. wc on low fire. * The furnace is
shipped with No. 44 orifices. Therefore, in this example all
main burner orifices must be changed and manifold pres
sure must be adjusted.
(7.) Multiply gas rate (cubic ft/hr) X heating value (Btu/
cubic ft).
(7.) Proceed to item c. to adjust manifold pressure.
Table 12-^Gas Rate Cu Ft/Hr
SECONDS
SIZE OF TEST DIAL
SECONDS
SIZE OF TEST DIAL
FOR 1
1
2
5
FOR 1
1
2
5
REVOLUTION
CU ft
CU ft
CU ft
REVOLUTION
CU ft
CU ft
cu ft
10
360
720
1800
50
72
144
360
11
327
655
1636
51
71
141
355
12
300
600
1500
52
69
138
346
13
277
555
1385
53
68
136
340
14
257
514
1286
54
67
133
333
15
240
480
1200
55
65
131
327
16
225
450
1125
56
64
129
321
17
212
424
1059
57
63
126
316
18
200
400
100
58
62
124
310
19
189
379
947
59
61
122
305
20
180
360
900
60
60
120
300
21
171
343
857
62
58
116
290
22
164
327
818
64
56
112
281
23
157
313
783
66
54
109
273
24
150
300
750
68
53
106
265
25
144
288
720
70
51
103
257
26
138
277
692
72
50
100
250
27
133
267
667
74
48
97
243
28
129
257
643
76
47
95
237
29
124
248
621
78
46
92
231
30
120
240
600
80
45
90
225
31
116
232
581
82
44
88
220
32
113
225
563
84
43
86
214
33
109
218
545
86
42
84
209
34
106
212
529
88
41
82
205
35
103
206
514
90
40
80
200
36
100
200
500
92
39
78
196
37
97
195
486
94
38
76
192
38
95
189
474
96
38
75
188
39
92
185
462
98
37
74
184
40
90
180
.450
100
36
72
180
41
88
176
439
102
35
71
178
42
86
172
429
104
35
69
173
43
84
167
419
106
34
68
170
44
82
164
409
108
33
67
167
45
46
47
80
78
76
160
157
153
400
391
383
110
112
116
120
33
32
31
30
65
64
62
60
164
161
155
48
49
75
73
150
147
375
367
150
b. Check gas input rate by clocking gas meter for low and
high fire.
(1.) Obtain average yearly heat value for local gas supply.
NOTE: Be sure heating value used for calculations is correct for
your altitude. Consult local gas utility for altitude adjustments of
gas heating value.
(2.) Check and verify orifice size in furnace. NEVER
ASSUME THE ORIFICE SIZE. ALWAYS CHECK
AND VERIFY.
(3.) Turn off all other gas appliances and pilots.
(4.) Turn SW2 to ON. Close R to W/Wl and jumper R to
W2 to start furnace in high fire and let run for 3
minutes.
(5.) Measure time (in sec) for gas meter to complete 1
revolution.
(6.) Refer to Table 12 for cubic ft of gas per hour.
EXAMPLE;
Btu heating input=Btu/cu ft X cu ft/hr
Heating value of gas 1070 Btu/cu ft
Time for 1 revolution of 2-cu/ft dial 72 sec
Gas rate= 100 X 1070=107,000 Btuh
(8.) Measured gas input should equal low and high fire gas
inputs on unit rating plate, ± 2 percent.
NOTE: High altitude—In the United States, gas input on rating
plate is for altitudes up to 2000 ft. Ratings for altitudes over 2000
ft MUST be reduced 4 percent for each 1000 ft above sea level. To
obtain the altitude-adjusted rating, adjust the manifold pressure,
item c., and replace the main burner orifices as needed. Refer to
National Fuel Gas Code Appendix F, Table F-4 for proper orifice
sizing at high altitudes.
NOTE: Canadian installations only—The Canadian ratings are
approved for altitudes up to 2000 ft for natural and propane gases.
High-altitude ratings are from 2000 ft to 4500 ft above sea level.
High-altitude rating includes a 10 percent derate as required by
Canadian standards.
(9.) Remove jumper R to W2 and repeat items 5 through 8
for low fire.
(10.) Proceed to item c. to adjust manifold pressure.
A CAUTION
DO NOT redrill burner orifices. Improper drilling (burrs, out
of round, etc.) can cause excessive burner operating noise and
misdirection of burner flames. This could result in flame
impingement on burners and heat exchanger surfaces, leading
to potential failures.
c. Adjust gas input.
(1.) Move SW2 to the ON position (See Fig. 13.) to lock
furnace in low-fire. Jumper R to W/Wl to call for low
gas heat.
(2.) Remove gas control regulator adjustment seal caps.
(See Fig. 13.)
(3.) Turn low-fire adjusting Screw (5/64-in. hex Allen
wrench) counterclockwise (out) to decrease input rate
or clockwise (in) to increase rate. When adjusting
input rate, DO NOT set manifold pressure less than
1.3-in. wc or more than 1.7-in. wc for natural gas. If
manifold pressure is outside this range, change main
burner orifices.
(4.) Turn SW2 to the OFF position after low-fire adjust
ment.
(5.) Jumper R-to-W/Wl terminal connections on control to
keep furnace in high-fire adjustment.
(6.) Turn high-fire adjusting screw (5/64-in. hex Allen
wrench) counterclockwise (out) to decrease input rate
or clockwise (in) to increase rate. When adjusting
input rate, DO NOT set manifold pressure less than
3.2-in wc or more than 3.8-in. wc for natural gas. If
manifold pressure is outside this range, change main
burner orifices.
NOTE: If orifices are changed, both high fire and low fire input
rates must be readjusted, with manifold pressures within ranges
specified in items 3 and 6.
16