beautypg.com

A caution, Table 12-^gas rate cu ft/hr – Carrier 58TUA User Manual

Page 16

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

EXAMPLE:
Heat value 1040
Btu/cu ft specific gravity 0.62
Therefore; Orifice No. 45* with manifold pressure 3.7-in.
wc on high fire and 1.6-in. wc on low fire. * The furnace is
shipped with No. 44 orifices. Therefore, in this example all
main burner orifices must be changed and manifold pres­
sure must be adjusted.

(7.) Multiply gas rate (cubic ft/hr) X heating value (Btu/

cubic ft).

(7.) Proceed to item c. to adjust manifold pressure.

Table 12-^Gas Rate Cu Ft/Hr

SECONDS

SIZE OF TEST DIAL

SECONDS

SIZE OF TEST DIAL

FOR 1

1

2

5

FOR 1

1

2

5

REVOLUTION

CU ft

CU ft

CU ft

REVOLUTION

CU ft

CU ft

cu ft

10

360

720

1800

50

72

144

360

11

327

655

1636

51

71

141

355

12

300

600

1500

52

69

138

346

13

277

555

1385

53

68

136

340

14

257

514

1286

54

67

133

333

15

240

480

1200

55

65

131

327

16

225

450

1125

56

64

129

321

17

212

424

1059

57

63

126

316

18

200

400

100

58

62

124

310

19

189

379

947

59

61

122

305

20

180

360

900

60

60

120

300

21

171

343

857

62

58

116

290

22

164

327

818

64

56

112

281

23

157

313

783

66

54

109

273

24

150

300

750

68

53

106

265

25

144

288

720

70

51

103

257

26

138

277

692

72

50

100

250

27

133

267

667

74

48

97

243

28

129

257

643

76

47

95

237

29

124

248

621

78

46

92

231

30

120

240

600

80

45

90

225

31

116

232

581

82

44

88

220

32

113

225

563

84

43

86

214

33

109

218

545

86

42

84

209

34

106

212

529

88

41

82

205

35

103

206

514

90

40

80

200

36

100

200

500

92

39

78

196

37

97

195

486

94

38

76

192

38

95

189

474

96

38

75

188

39

92

185

462

98

37

74

184

40

90

180

.450

100

36

72

180

41

88

176

439

102

35

71

178

42

86

172

429

104

35

69

173

43

84

167

419

106

34

68

170

44

82

164

409

108

33

67

167

45
46
47

80
78
76

160
157
153

400
391
383

110
112
116
120

33
32
31
30

65
64
62
60

164
161
155

48
49

75
73

150
147

375
367

150

b. Check gas input rate by clocking gas meter for low and

high fire.

(1.) Obtain average yearly heat value for local gas supply.

NOTE: Be sure heating value used for calculations is correct for

your altitude. Consult local gas utility for altitude adjustments of
gas heating value.

(2.) Check and verify orifice size in furnace. NEVER

ASSUME THE ORIFICE SIZE. ALWAYS CHECK
AND VERIFY.

(3.) Turn off all other gas appliances and pilots.

(4.) Turn SW2 to ON. Close R to W/Wl and jumper R to

W2 to start furnace in high fire and let run for 3
minutes.

(5.) Measure time (in sec) for gas meter to complete 1

revolution.

(6.) Refer to Table 12 for cubic ft of gas per hour.

EXAMPLE;
Btu heating input=Btu/cu ft X cu ft/hr
Heating value of gas 1070 Btu/cu ft
Time for 1 revolution of 2-cu/ft dial 72 sec

Gas rate= 100 X 1070=107,000 Btuh

(8.) Measured gas input should equal low and high fire gas

inputs on unit rating plate, ± 2 percent.

NOTE: High altitude—In the United States, gas input on rating

plate is for altitudes up to 2000 ft. Ratings for altitudes over 2000
ft MUST be reduced 4 percent for each 1000 ft above sea level. To
obtain the altitude-adjusted rating, adjust the manifold pressure,
item c., and replace the main burner orifices as needed. Refer to
National Fuel Gas Code Appendix F, Table F-4 for proper orifice
sizing at high altitudes.

NOTE: Canadian installations only—The Canadian ratings are
approved for altitudes up to 2000 ft for natural and propane gases.

High-altitude ratings are from 2000 ft to 4500 ft above sea level.
High-altitude rating includes a 10 percent derate as required by

Canadian standards.

(9.) Remove jumper R to W2 and repeat items 5 through 8

for low fire.

(10.) Proceed to item c. to adjust manifold pressure.

A CAUTION

DO NOT redrill burner orifices. Improper drilling (burrs, out
of round, etc.) can cause excessive burner operating noise and
misdirection of burner flames. This could result in flame
impingement on burners and heat exchanger surfaces, leading
to potential failures.

c. Adjust gas input.

(1.) Move SW2 to the ON position (See Fig. 13.) to lock

furnace in low-fire. Jumper R to W/Wl to call for low
gas heat.

(2.) Remove gas control regulator adjustment seal caps.

(See Fig. 13.)

(3.) Turn low-fire adjusting Screw (5/64-in. hex Allen

wrench) counterclockwise (out) to decrease input rate
or clockwise (in) to increase rate. When adjusting
input rate, DO NOT set manifold pressure less than

1.3-in. wc or more than 1.7-in. wc for natural gas. If

manifold pressure is outside this range, change main
burner orifices.

(4.) Turn SW2 to the OFF position after low-fire adjust­

ment.

(5.) Jumper R-to-W/Wl terminal connections on control to

keep furnace in high-fire adjustment.

(6.) Turn high-fire adjusting screw (5/64-in. hex Allen

wrench) counterclockwise (out) to decrease input rate
or clockwise (in) to increase rate. When adjusting
input rate, DO NOT set manifold pressure less than
3.2-in wc or more than 3.8-in. wc for natural gas. If
manifold pressure is outside this range, change main
burner orifices.

NOTE: If orifices are changed, both high fire and low fire input

rates must be readjusted, with manifold pressures within ranges
specified in items 3 and 6.

16