beautypg.com

Refrigerant charging, Catltiof^; to pfeveat persotial fejury. 'wear, Safeij; giasoe» ao<3 giovfes ha»d3t»g – Carrier 50QT User Manual

Page 5

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

#

When an internal overload is suspected of being
open, check by using an ohmmeter or continuity
tester.

If

necessary,

refer

to

Carrier

Standard

Service Techniques Manual, Chapter 2, Electrical,

for complete instructions.

Defrost Control, consisting of a defrost timer,
defrost

thermostat

and

defrost

relay,

interrupts

normal system heating operation to remove frost
and ice formation on outdoor coil. Frost impairs
unit

performance.

Defrost

control

simultaneously

stops outdoor fan, energizes reversing valve sole­
noid to switch system into cooling cycle (outdoor

unit

as

condenser,

indoor

unit

as

evaporator),

and

activates

electric

heater.

Unit

can

defrost

every 90 minutes, but will do so only if outdoor
temperatures are in the frosting temperature zone.

For heat pump to defrost, 2 conditions are

necessary:

1. Defrost timer contacts must be closed.

2. Coil temperature must be cold enough to cause

defrost thermostat contacts to close.

Contacts close at 28 ±3 F (50QT112 - 118) and

35 ± 3 F (50QT124, 130). Every 90 minutes of

elapsed running time, the defrost timer contacts
close for 10 seconds. If the defrost thermostat
contacts are closed, the unit defrosts. The defrost

timer

limits

defrosting

period

to

10

minutes.

Normally the frost is removed and the defrost ther­
mostat contacts will open to terminate defrosting

before 10 minutes have elapsed. Defrost thermostat
contacts open at 65 ±5F (50QT112 - 118) and
75

±5F

(50QT124,130).

When

defrosting

is

terminated, the outdoor fan motor is energized
and reversing valve solenoid is de-energized, re­
turning unit to heating cycle.

HEAT PUMP CIRCUITS shown in Fig. 4 are
refrigerant flow diagrams for heating and cooling

cycles.

Refrigerant Charging

CAtlTiOf^; To pfeveat persotial fejury. 'wear

safeij; giasoe» ao<3 giovfes

ha»d3t»g

Table 2 — Service Data

Do not overcharge system. An overcharge can

cause compressor flooding.

Unit refrigerant system is factory charged. When

recharging is necessary, weigh in total charge indi­
cated in Table 2. (Charge must be weighed in during

heating season.) Remove any refrigerant remaining
in system before recharging. If system has lost com­

plete charge, triple-evacuate system to 5000 microns
(29.7 in. vacuum) before recharging. Service port
connections are provided on unit suction and dis­
charge lines for evacuation and charging. (See Fig. 4

for service port location.) Dial-a-charge charging
cylinder is an accurate device used to recharge

systems by weight. These cylinders are available at
refrigeration supply firms.

UI\IIT50QT

112

115

118

124

130

MODEL

300

300

300

300

300

R-22 CHARGE* (lb)

2 7

2 7

3 2

4 5

47

Refrig Control

AccuRater™ Bypass Type

INDOOR FAN

Centrifugal Blower,

Direct Drive, 2-Speed

Rotationt

CW

CW

CW

CCW

CCW

Rpm

1580

1550

1570

1675

1675

Diameter (in )

6

6

6

7

7

Width (in.)

8

430/

550/

575/

885/

1025/

Range (cfm)

375

475

480

800

960

Motor Hp

'A

'A

Vs.

'/4

V4

OUTDOOR FAN

Propeller, Direct Drive, Single Speed

Cfm

1700

1700

1700

2000

2000

Rpm

1125

Diameter (in )

15

Motor Hp

Vs

ccw

cw

Counterclockwise
Clockwise

‘Factory

refrigerant

charge

fLooking at fan motor shaft

To check and/or adjust charge during cooling

season, use Cooling Cycle Charging Charts (Fig. 5,
7, 9, II, 13) and follow Charging Chart Method
below. The charging chart may also be used as an
alternate method of recharging system.

To check

system operation

during heating cycle,

use Heating Cycle Operation Check Chart (Fig. 6, 8,

10, 12, 14). These charts indicate whether a correct

relationship exists between system operating pres­
sures and air temperatures entering unit. If pressure

and temperature lines do not intersect on chart,
the system refrigerant charge may not be correct
or other system abnormalities may exist. Do not
use Operating Check Charts to adjust refrigerant
charge. Weigh charge into system.

COOLING CYCLE CHARGING CHART

METHOD

1. Operate unit a minimum of 10 minutes before

checking charge, and after each charge

adjustment.

2. Measure suction pressure by attaching a gage to

unit suction service port. (See Fig. 4 for correct
service port location.)

3. Measure outdoor (coil inlet) air dry-bulb tem­

perature. Use service thermometer.

4. Using a sling psychrometer, measure wet-bulb

temperature of air entering indoor fan coil.

5. Refer to Charging Chart. Locate on curves where

outdoor air dry-bulb and indoor air wet-bulb
temperature lines intersect.

6.

From intersect point, project vertically down­

ward to chart suction pressure line. Compare
chart suction pressure to unit suction pressure
(Step 2).

7. If unit suction pressure is lower than chart pres­

sure,

add

refrigerant

to

system

until

chart

pressure is reached. If unit suction pressure is
higher than chart pressure, remove refrigerant
until chart pressure is reached.