Table 1 — electrical data (&©^zt – Carrier 50QT User Manual
Page 2
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Table 1 — Electrical Data (&©^zt
MODEL
50QT
V/PH
OPER
VOLTAGE^
COMPR
IFM OFM
ELECTRIC
HEATER
AMPS
BRANCH CIRCUIT #1
(or Total Unit)t
BRANCH CIRCUIT #2
(When Used)t
Max Fuse or
HACR Ckt
Bkr Ampst
MCA
Max Fuse or
HACR Ckt
Bkr Ampst
MCA
Max
Min^*
LRA
RLA
FLA
FLA
AB
112300 II
208/230/1
254
187
37
6 8
1 5
1 0
9 4/12 5
18.0/20.8
25/30
35/40
22 8/26 6
33.5/37.0
—
—
115300
208/230/1
254
187
43
8 7
1 5
1 0
9 4/12 5
18 0/20 8
25/30
35/40
25 1/29 0
35.9/39.4
—
—
AB
118300 AD
AF
208/230/1
254
187
49
10 3
1 7
1 0
9 4/12 5
18 0/20 8
26 8/31 3
30/35
40/45
50/55
27 3/31 2
38 1/41 6
49 1/54 7
—
—
AD
124300 AF
AG
208/230/1
254
187
59
13 0
2 0
1 5
17 3/20 8
26 8/31 3
36 1/41.7
45/50
55/60
41 4/45 9
53.6/59.1
AD
130300 AF
AG
208/230/1
254
187
79
16 9
2 4
1 5
17 4/ 20 8
26 8/31 3
36 0/41 7
.....
50
/55 ^ 1 47.5/52J
1
♦Permissible limits of the voltage range at which units will
operate satisfactorily
fField wiring to be sized for NEC or local codes Use copper wire
only
^Maximum dual element fuse
♦♦Minimum voltage is 197 when outdoor ambient temperature
exceeds 105 F
NOTE: Dual values in this table (for example Electric Fleeter Amps
9 4/12 5) apply to 208- and 230-volt connections respectively
These units require 2 separate supply circuits
Refer to BOTFI branch circuit charts for complete
electrical data
FLA
— Full Load Amps
FIACR
— Heating, Air Conditioning
and Refrigeration
IFM
— Indoor Fan Motor
LRA
— Locked Rotor Amps
MCA—
Minimum Circuit
Amps
OFM
— Outdoor Fan Motor
RLA
— Rated Load Amps
♦INSPECT EQUIPMENT for damage prior to in
stallation. To remove plastic wrapper, grasp bottom
and pull out until velcro strips separate. To remove
metal cover plate, remove 6 screws. Eile claim with
shipping
company
if
shipment
is
damaged
or
incomplete.
Leave chassis bolted to skid and replace metal
cover plate, plastic wrapper, and carton until ready
for installation into wall sleeve.
INSPECT
WALL
SLEEVE
installation
for
damage. Condensate drain pan must be free of
debris and installed in accordance with local build
ing regulations. Electrical connector on left side of
sleeve should be free of dirt, grease, paint, etc.
Connector must be properly wired before chassis
installation. Duct connection panel must be level
and duct connections complete. Do not rest weight
of ductwork on duct connector panel. Inspect name
plate on sleeve to ensure wire and fuse sizing is
correct for model size to be installed.
At ^
-i
Fig. 1 — Chassis with Indoor Plastic Wrapper
©