beautypg.com

Carrier 50DP016 User Manual

Page 6

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Step 3 — Field Fabricate Ductwork — Secure all
ducts to building structure. Use flexible duct connectors
between unit and ducts as required. Insulate and weather­
proof all external ductwork, joints and roof openings

with flashing and mastic in accordance with applicable
codes.

Ducts passing through an unconditioned space must

be insulated and covered with a vapor barrier.

A minimum clearance is not required on 50DP,

DPE012,014 and 50DP016 units. The 50DP020 units
with electric heat require one-in. clearance the first 24 in.
of ductwork.

Outlet grilles must not lie directly below unit discharge.

Step 4 — Make Unit Duct Connections — Unit
is shipped for through-the-bottom duct connections.
Ductwork openings are shown in Fig. 1 and 4. Duet
connections are shown in Fig. 5. Field-fabricated con­
centric ductwork may be connected as shown in Fig. 6 and

7. Attach all ductwork to roof curb and roof curb base-
pans. Refer to installation instructions shipped with
accessory roof curb.

I

NOTE: Do not drill in this area, damage to basepan may resuit
In water ieak

Fig. 6 — Concentric Duct Air Distribution

50DR DPE0I2.0I4 50DP0I6
INDOOR FAN MOTOR

NOTE: Do not drill in this area, damage to basepan may result
in water leak.

Fig. 5 — Air Distribution — Through-the-Bottom

Step 5 — Trap Condensate Drain — See Fig. 4

and 8 for drain location. Plug is provided in drain hole
and must be removed when unit is operating. One 3/4-in.
half coupling is provided inside unit evaporator section
for condensate drain connection. An 8-1/2in. x 3/4-in.
diameter and 2-in. x 3/4-in. diameter pipe nipple coupled
to standard 3/4-in. diameter elbows provide a straight

path down through holes in unit base rails (see Fig. 9).
A trap at least 4 in. deep must be used and must be pro­
tected against freeze-up.

NOTE: Dimension A, A1 and B, B1 are obtained from field-
supplied ceiling diffuser.

Fig. 7 — Concentric Duct Details

y--:

CONNECTION

Fig. 8 — Condensate Drain Details

11 DRAIN HOLES