Table 1b — Physical Data — 50DP016,020
UNIT SIZE
50DP016
50DP020
OPERATING WEIGHT (lb)
Unit (Outdoor Coil/Indoor Coil)
AI/AI
Al/Cu
Cu/Cu
Roof Curb
Economizer
Electric Heat
1470
1550
1630
1980
2110
2220
200
110
65
COMPRESSOR
Quantity...Type
1 .06DA537
Semi-Hermetic — 6 Cylinders
2. 06DA824
OH (oz)
160
160 ea
REFRIGERANT
R-22
R-22
Charge (lb) Sys 1*. Sys 2
21.2
17.0, 17.0
REFRIGERANT METERING DEVICE
Capillary Tubes
U|»er Circuit
Quantity...Length...ID/OD (in.)
6 40 0 065/0 125
13 25 0 055/0 125
Lower Circuit
Quantity ...Length...ID/OD (in.)
6 20 .0 055/0 125
6...20 ..0 055/0 125
13. .25.0 055/0 125
OUTDOOR COIL
Copper Tubes, Aluminum or Copper Plate Fins
Rows
3
4
Fins/in.
Aluminum
13.6
136
Copper
124
124
Totai Face Area (sq ft)
18.9
22.2
OUTDOOR AIR FAN
Propeller Type, Direct Drive
Nominal Cfm
12,000
11,400
Number...Dlameter (in.)
2 26
2 .26
Motor Hp (1075 Rptn)
1
1
INDOOR COIL
Copper Tubes, Aluminum or Copper Plate Fins
Rows
3
4
FIns/ln.
Aluminum
14.3
14.4
Copper
13.1
13 1
Totai Face Area (sq ft)
16.5
17.9
INDOOR AIR FANf
Centrifugal, Belt Drive
Quantity ...Size (in.)
2 .10x10
2 .12x12
Nominal Cfm
6000
7200
Rpm Range Std
916-1186
—
Opt
1158-1428
—
Pulley A
—
848
Pulley B
—
1060
Maximum Aiiowabie Rpm
1550
1550
Motor Puiley Pitch Diameter (in.) Std
3 4-4.4
—
Opt
4 3-5 3
—
Puiiey A
—
32
Puiiey B
—
4.0
Fan Puiiey Pitch Diameter (in.)
6.4
6.6
Belt, Quantity...Type...Length (in.)
1 V.45
2 ..V 45
SpeedChangeperFuilTurn Std
54
—
of Moveable Pu Iley Flange (R pm) Opt
55
—
Moveable Pulley Max Full Turns
from Closed Position
5
—
Factory Setting — Full Turns Open
35
—
Factory Speed Setting (Rpm) Std
970
—
Opt
1240
—
Puiiey A
—
848
Puiiey B
—
1060
Motor Hp (Service Factor) Std
3 (1.15)
5 (1 15)
Opt
—
—
HIGH-PRESSURE SWITCH
Cutout (psig)
Reset (psig)
428
320
LOW-PRESSURE SWITCH (Liquid Line)
Cutout (psig)
Reset (psig)
27
60
AiR INLET SCREENS
Economizer, Number...Size (in.)
2 20x25x1
1...20x20x1
INDOOR AIR FILTERS (Type)
Number...Size (in.)
10% efficient
2. 20x20x2
3.16x20x2
2.16x25x2
Disposable Fiberglass
4 20x20x2
4 16x20x2
'System 1 consists of upper portion of outdoor coil and lower
portion of indoor coii, except for size 020 which is intertwined
t016 unit has adjustable standard and aiternate drives The 020
unit does not have an aiternate drive, but has 2 non-adjustable
pulieys Puiiey A is installed in unit; puiley B is shipped with unit