beautypg.com

Carrier 50DP016 User Manual

Page 4

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Table la — Physical Data — 50DP,DPE012,014

UNIT SIZE

50DP012

50DPE012

50DP014

50DPE014

OPERATING WEIGHT (lb)

Unit (Outdoor Coil/Indoor Coil)

AI/AI

1180

1260

1260

1470

Al/Cu

1230

1340

1340

1550

Cu/Cu

1280

1410

1410

1630

Roof Curb

200

Economizer

110

Electric Heat

65

Alternate Motor and Drive

5

COMPRESSOR

Hermetic — 2 Cylinders

Semi-Hermetic — 6 Cylinders

Quantity...Type

2. .P64

1 P56, 1 P60

2. .P77

1 ..06DA328

Oil (oz)

76 ea

76 ea

76 ea

160

i

REFRIGERANT

Charge (lb) Sys 1* Sys 2

7.9, 6.6

10.9, 12.5

±

R-22

8 3, 8 4

20.8

REFRIGERANT METERING DEVICE

Upper Circuit

Quantity...Length...lD/OD (in.)

Lower Circuit

Capillary Tubes

7 .35 0 055/0 125 8 34.0.055/0 125 8.. 44. 0 065/0.125

6...25 0 055/0 125
6. 25 0 055/0.125
6 .25.. 0 055/0.125

Quantity...Length...ID/OD (in.)

6.. 20...0.055/0 125

7...20 .0.055/0 125

7...35...0.065/0.125

OUTDOOR COIL

Copper Tube, Aluminum or Copper Plate Fins

Rows

2

3

3

3

Fins/in.

Aluminum

13.6

13.6

136

136

Copper

124

12.4

12.4

124

Total Face Area (sq ft)

18.9

18.9

18.9

18.9

OUTDOOR AIR FAN

Propeller Type, Direct Drive

Nominal Cfm

9000

8000

8000

12,000

Quantity...Diameter (in.)

2. 22

2. .22

2...22

2...26

Motor Hp (1075 Rpm)

V2

’/2

'k

1

INDOOR COIL

Copper Tube, Aluminum or Copper Plate Fins

Rows

2

3

3

3

Fins/in.

Aluminum

144

156

156

14.3

Copper

13.1

14.2

14.2

13 1

Total Face Area (sq ft)

14.7

13.8

13.8

16.5

INDOOR AIR FANt

Centrifugal, Belt Drive

Quantity...Size (in.)

2 10x10

2 ..10x10

2 .10x10

2...10x10

Nominal Cfm

4000

4000

5000

5000

Rpm Range

Std

753-1066

805-1093

805-1093

805-1093

Opt

878-1191

978-1265

978-1265

978-1265

Max Allowable Rpm

1550

1550

1550

1550

Motor Pulley Pitch Diameter (in.)

Std

2 4-3 4

2 8-3 8

2.8-3.8

2 8-3 8

Opt

2.8-3.8

3 4-4 4

3 4-4.4

3 4-4 4

Fan Pulley Pitch Diameter (in.)

5.5

6.0

6.0

6.0

Belt, Quantity...Type...Length (in.)

1 V. 41

1 V. 43

1 V. 43

1. V...43

Speed Change per Full Turn

Std

62

58

58

58

of Moveable Pulley Flange (Rpm)

Opt

63

57

57

57

Moveaable Pulley Max Full Turns

from Closed Position

Factory Setting — Full Turns Open

3 5

3

35

3

Factory Speed Setting (Rpm)

Std

846

920

891

920

Opt

972

1092

1063

1092

Motor Hp (Service Factor)

Std

1 (1.25)

2 (1 15)

2 (1.15)

2 (1 15)

Opt

1’/2 (1.20)

3 (1.15)

3 (1.15)

3 (1.15)

HIGH-PRESSURE SWITCH

Cutout (psig)

428

Reset (psig)

320

LOW-PRESSURE SWITCH (Liquid Line)

Cutout (psig)
Reset (psig)_______________________

27
60

AIR INLET SCREENS

Economizer, Number...Size (in.)

2 .20x25x1

1...20x20x1

iNDOOR AIR FILTERS (Type)

Number...Size (in.)

10% efficient — Disposable Fiberglass

2.16x20x2
4 .16x25x2

2. .16x20x2
4 16x25x2

2..

.16x20x2

4..

.16x25x2

2 .20x20x2
3 16x20x2
2.16x25x2

‘System 1 consists of upper portion of outdoor coil and lower portion of indoor coil

fUnits have adjustable standard and alternate drives