Table 4 — Air Quantity Limits

UNIT MODEL

MIN CFM

MAX CFM

50DP,DPE012

3000

5000

50DP,DPE014

3750

6250

50DP016

4500

7500*

50DP020

5400

9000

'Indoor Fan Max Watts = 3000

HEATING — Turn on main power to unit. Set system
selector switch at HEAT, fan switch at AUTO.; and

thermostat at a setting above room temperature. First

stage of electric heater elements are energized on closing
of heating contact No. 1 in thermostat. On a further fall
of room temperature, heater contact No. 2 closes ener­
gizing second-stage electric heater elements.
To Shut Off Unit — Set system selector switch at OFF.

#

Indoor Air Fan — Fan belts and pulleys are factory
installed. Belts are secured to pulleys with tape.
Remove tape and, if required, adjust as described in
Service, Indoor Air Fan Adjustment.

50DP020 has 2 non-adjustable pulleys. Pulley A is

installed in unit. Pulley В is shipped in cardboard box
taped to vestibule below main control box.

Outdoor Air Fans and Motors are factory set. Refer
to Service, Outdoor Air Fan Adjustment as required.

Return Air Filters — Check that correct filters are
installed in filter tracks. See Table 1. Do not operate unit

without return air filters.

Outdoor Air Inlet Screens — Outdoor air inlet
screens must be in place before operating unit.

Economizer

Section

Remove

filter

access

panel. Check that outdoor air damper is closed and return
air damper is open.

Economizer operation and adjustment is described in

Start-Up, Economizer Operation; and Service, Econo­
mizer Adjustment, respectively.

Base Unit Operation
COOLING — Unit power on. System selector switch at

COOL; fan switch at AUTO.; thermostat at a setting
below room temperature.
50DPE014 and 50DP016 — Compressor starts unloaded

on closure of No. 1 contact in thermostat.

Additional rise in room temperature closes contact

No. 2 in thermostat which de-energizes the unloader coil.
Compressor is now fully loaded.

Check cooling effects at a setting below room tempera­

ture. Check unit charge. Refer to Service, Refrigerant

Charge.

Reset thermostat at a temperature above room tem­

perature. Compressor(s) will shut off.
50DP,DPE012 and 50DP014.020 — Upon a rise in room

temperature, cooling contact No. 1 in the thermostat
closes, energizing the first-stage cooling contactor and the
indoor fan contactor. The first-stage compressor, out­

door fan motor and indoor fan motor start and run.

Upon a further rise in room temperature, cooling

contact No. 2 in the thermostat closes, energizing the
second-stage

cooling

contactor.

The

second-stage

compressor starts and runs.
To Shut Off Unit — Set system selector switch at OFF

position or reset thermostat above room temperature.
Units with Signal-LOC™ protection device shut down on
any safety trip and thermostat light comes on. Determine
reason for safety trip. Restart 50DPE014 and 50DP016,
020 compressor(s) by resetting circuit breaker at unit.

VENTILATION

AIR

CIRCULATION

(Continuous

Fan) — Unit power on. System selector switch at OFF,
HEAT or COOL; fan switch set at ON. Indoor fan con­
tactor is energized through the switch on the thermostat,

and the indoor fan runs continuously.

AUTOMATIC

CHANGEOVER

(with

Autqmatic

Changeover Thermostat) — System selector switch set
at AUTO. When temperature of conditioned space rises
to cooling selector lever setting, unit automatically
switches from heating mode to cooling mode. When tem­
perature of the conditioned space falls to the heating

selector lever setting, unit automatically changes from
cooling mode to heating mode. The thermostat is inter­
locked so that cooling and heating systems do not operate

at the same time.

HEAD PRESSURE CONTROL — All units have fan

cycling thermostats which, at 55 F, shut off one outdoor
fan motor. This permits unit to operate down to 40 F

outdoor air temperature.

Economizer Operation — If unit is equipped with
modulating outdoor air control (economizer), it should
operate as follows;

COOLING MODE — Indoor and outdoor fans and com­
pressor energize when there is a call for cooling and

enthalpy of outdoor air is above enthalpy control setting.
The economizer damper moves to VENT position.

Indoor fan starts and economizer damper opens fully

on a first-stage call for cooling when enthalpy of outdoor
air is below the enthalpy control setting. Compressor
remains off.

Compressor is energized and mechanical cooling

integrates with economizer cooling upon a second-
stage call for cooling. If outdoor air temperature falls

below 50 F, cooling lockout switch prevents compressor
from operating.

Economizer damper modulates when mixed air tem­

perature is below mixed air thermostat setting.

A freeze protection thermostat (FPT) is located on the

indoor coil. It detects ice buildup and turns off the
compressor, thus allowing the coil to clear. Once ice
melts, the compressor can be re-energized.

HEATING MODE — Outdoor air damper stays at
VENT position while indoor air fan runs.
NOTE: If fan switch is at ON position, and room thermo­
stat is satisfied, damper goes to ventilation position.