Packaged Heating/Cooling Units
Constant Volume Application
HVAC Guide Specifications
Size Range: I V
2
to 5 Tons, Nominal Cooling
40,000 to 140,000 Btuh,
Nominal Input Heating
Carrier Model Number 48SS
Part 1 — General
1 01 SYSTEM DESCRIPTION
A Outdoor rooftop mounted, gas heating/electric cool
ing unit utilizing a rotary, reciprocating, or scroll her
metic compressor for cooling duty Unit shall discharge
supply air downward or horizontally as shown on con
tract drawings Outdoor fan/coil section shall have a
blow-thru design for minimum sound levels.
1 02 QUALITY ASSURANCE
A Unit shall be rated in accordance with ARl Standards
210/240-89 and 270-84
B Unit shall be designed in accordance with UL Stand
ard 564.
C Unit shall be UL listed and CSA certified as a total
package for safety requirements
D Roof curb shall be designed to conform to NRCA
Standards
E Insulation and adhesive shall meet NFPA 90A re
quirements for flame spread and smoke generation
F Cabinet insulation shall meet ASHRE standard
no 62P
1 03 DELIVERY, STORAGE, AND HANDLING
A Unit shall be stored and handled per manufacturer’s
recommendations
Part 2 — Products
2 01 EQUIPMENT
A General
Factory-assembled, single-piece heating and cooling
unit Contained within the enclosure shall be all fac
tory wiring, piping, controls, refrigerant charge (R-22),
and special features required prior to field start-up
B Unit Cabinet'
1 Unit cabinet shall be constructed of phosphated,
zinc-coated prepainted steel, capable of withstand
ing 500 hours in salt spray
2 Cabinet panels shall be easily removed for
servicing
3 Indoor blower compartment interior cabinet sur
faces shall be insulated with a minimum Vz-in. thick,
flexible fiberglass insulation, coated on the air side.
Aluminum foil-faced fiberglass insulation shall be
used in the entire section
C. Fans.
1 The indoor (evaporator) fan shall be 2- or 3-speed
direct-drive, as shown on equipment drawings
2 Fan wheel shall be made from steel, be double
inlet type with forward curved blades with corro
sion resistant finish and be dynamically balanced.
3 Outdoor (condenser) fan shall be of the direct driven,
propeller type with aluminum blades riveted to cor
rosion resistant steel spiders, be dynamically bal
anced, and discharge air vertically upwards and
horizontally
D Compressor:
1 Fully hermetic compressor with factory-installed vi
bration isolation
2 Rotary compressors shall be standard on unit size
018 Reciprocating compressors shall be standard
on unit sizes 024-042 Scroll compressors shall be
standard on unit sizes 048 and 060.
E Coils
Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless copper
tubes with all joints brazed Tube sheet openings shall
be belled to prevent tube wear.
F Heating Section.
1 Induced-draft combustion type with energy saving
direct spark ignition system and redundant main
gas valve
2. Induced-draft motors shall be provided with solid-
state hall effects sensor to ensure adequate airflow
for combustion
3 The heat exchangers shall be constructed of alu
minized steel for corrosion resistance
4 Burners shall be of the in-shot type constructed of
aluminum coated steel
5 Integrated gas control board shall provide control
of heating and simplify troubleshooting through its
built-in diagnostic function.
6. All gas piping and electric power shall enter the unit
cabinet at a single location
G. Refrigerant Components-
Refrigerant components shall be of the Acutrol”' feed
system type
H. Filter section shall consist of field-installed, throw
away, 1-in. thick fiberglass filters of commercially avail
able sizes
I. Controls and Safeties
1 Unit Controls.
a Unit shall be complete with self-contained low-
voltage control circuit.
2 Safeties.
Compressors shall incorporate a solid-state com
pressor protector which provides reset capability
25