UNIT
48SS
VOLTAGE
COMPRESSOR
COND.
FAN
INDOOR
POWER SUPPLY
AWG 60 C
MAX WIRE
V-PH-HZ
RANGE
MOTOR
FAN
MIN WIRE
LENGTH
FLA
SIZEt
(ft)
Min
Max
RLA
LRA
FLA
MCA
MOCP*
0
T8
......7 6
45
‘“07*
.........
120
15
14
75
024
124
61
0 7
20
182
30
12
80
030
14 4
82
1 4
20
21 8
30
10
100
036
208/230-1-60
187
253
18 0
96
1 4
28
26 7
40
10
90
042
20 4
104
1 4
40
30 9
50
8
100
048
26 4
129
2 1
50
40 1
60
6
100
060
32 1
169
2 1
68
49 0
60
6
100
030
94
66
1 4
20
15 5
25
12
80
036
11 7
75
1 4
28
18 8
30
12
65
042
208/230-3-60
187
253
14 0
91
1 4
40
22 9
35
10
85
048
15 0
99
2 1
50
25 9
40
10
75
060
19 3
123
2 1
68
33 0
50
8
90
036
5 6
40
0 8
1 4
92
10
14
100
042
048
460-3-60
414
506
64
82
42
50
0 8
1 1
20
23
10 8
13 7
15
20
14
14
100
100
060
10 0
62
1 1
32
16 8
25
12
100
LEGEND
AWG
— American Wire Gage
FLA
— Full Load Amps
HACR
— Heating, Air Conditioning
and Refrigeration
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP
— Maximum Overcurrent
Protection
NEC
— National Electrical Code
RLA
— Rated Load Amps
‘Fuse or HACR breaker
tMinimum wire size is based on 60 C copper wire If other than 60 C
wire is used, determine size from NEC Voltage drop of wire must be
less than 2% of rated voltage
NOTES:
1
In compliance with NEC requirements for multimotor and combina
tion load equipment (refer to NEC Articles 430 and 440), the over
current protective device for the unit shall be fuse or HACR breaker
The CSA units may be fuse or circuit breaker
2
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in suppiy voitage
is greater than 2% Use the following formula to determine the per
cent voltage imbalance
% Voltage Imbalance
max voltage deviation from average voltage
Example Supply voltage is 460-3-60
AB = 452
V
BC = 464
V
AC = 455
V
Average Voltage =
452 -I- 464 + 455
1371
3
= 457
Determine maximum deviation from average voltage
(AB) 457 - 452 = 5 v
(BC) 464 - 457 =7 v
(AC) 457 - 455 =2 v
Maximum deviation is 7 v
Determine percent voltage imbalance
% Voltage Imbalance = 100 x ——
457
= 1 53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%
100 x
IMPORTANT: If the supply voltage phase imbalance is more
than 2%, contact your local electric utility company immediately
average voltage
#
23