Cooling capacities (cont) – Carrier 48SS User Manual
Page 15
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

COOLING CAPACITIES (cont)
48SS048
TEMP (F)
AIR ENT
COND
EVAP AIR - CFM/BF
14ЦЦ/Ц.08 I 1600ЖТ0 I
Evap Air — Ewb (F)
1800/0.11
62
67
72
62
67
72
62
67
72
fc
43 8
48 3
52 9
44 5
49 1
53 7
45 1
49 6
53 9
85
SHC
39 4
32 7
25 6
41 9
34 6
26 4
44 1
36 4
27 1
kW
4 76
4 85
4 95
4 87
4 97
5 07
4 99
5 08
5 17
TC
41 9
46 4
50 9
42 6
47 0
51 7
43 3
47 5
52 2
95
SHC
38 6
32 1
24 8
41 1
33 9
25 9
43 1
35 9
26 8
kW
5 17
5 28
5 38
5 29
5 40
5 50
5 41
5 51
5 61
tc
39 3
44 2
48 8
40 1
44 7
49 2
41 2
45 2
49 6
105
SHC
37 3
31 2
24 1
39 7
33 1
25 1
41 2
35 1
26 0
kW
5 61
5 73
5.83
5 74
5 85
5.95
5 87
5 96
6 06
TC
36 6
41 5
46 4
37 7
42 4
47 0
39 0
42 8
47 4
115
SHC
35 9
30 2
23 4
37 6
32 4
24 3
39 0
34 2
25 4
kW
6 08
6 22
6.34
6 22
6 34
6 45
6 36
6 46
6 57
48SS060
EVAP AIR - CFM/BF
TEMP (F)
AIR ENT
COND
1750/0.03 [ 2Ö0O/0.Ц4 | 225Ц/0.Ц5
Evap Air — Ewb (F)
62
67
72
62
67
72
62
67
72
tc
55 0
62 Ö'
69“4
56 3
63 1
70 5
58 2
63 9
71 3
85
SHC
52 4
43 7
34 2
56 1
46 7
35 8
58 1
49 5
37 4
kW
6 14
6 33
6 53
6 32
6 50
6 70
6 52
6 67
6 88
TC
51 8
58 8
66 2
53 6
59 6
67 3
55 6
60 2
68 1
95
SHC
51 0
42 4
33 2
53 5
45 3
34 8
55 6
48 2
36 3
kW
6 62
6 82
7 05
6 83
7 00
7 22
7 03
7 17
7 39
TC
48 7
55 1
62 9
51 0
56 0
63 9
53 Ö
56 7
64 5
105
SHC
48 7
41 1
32 1
50 9
44 0
33 7
52 8
46 9
35 3
kW
7 17
7 37
7 60
7 39
7 54
7.78
7.59
7 71
7 95
TC
45 8
52 0
59 5
48 5
52 8
60 5
50 4
53 4
60 8
115
SHC
45 8
40 0
30 9
48 4
42 8
32 6
50 3
45 6
34 1
kW
7 77
7 94
8 19
7.98
8 12
8 36
8 18
8 29
8 43
LEGEND
Bypass Factor
Entering Wet-Bulb
Total Unit Power Input
Sensible Heat Capacity, 1000 Btuh
Total Cooling Capacity, 1000 Btuh (net)
BF -
Ewb —
kW
SHC
TC -
NOTES
1 Ratings are net, they account for the effects of the indoor-fan motor
power and heat.
2 Direct interpolation is permissible Do not extrapolate
3. The following formulas may be used.
.
_ sensible capacity (Btuh)
1 10 X cfm
Wet-bulb temperature corresponding to enthalpy of air
leaving indoor coil (hi^b)
total capacity (Btuh)
4 5
X
cfm
Where hgwb = Enthalpy of air entering indoor coil
The SHC is based on 80 F edb temperature of air entering indoor
coil
Below 80 F edb, subtract (corr factor x cfm) from SHC
Above 80 F edb, add (con factor x cfm) to SHC
Correction Factor = 1 10 x (1 - BF) x (edb - 80)
t|db
*lwb
h|wb “ h ewb ~
15