Carrier 30HK User Manual
Page 9
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
The electric heater is wired into the 115-volt
control circuit thru normally closed contacts of
control relay in such a way that it is energized only
when compressor is not operating.
All heaters are 125 watts.
C .\L 1 ION: Never open an\ >witeh or discon
nect that will de-encrgi/e crankcase healer un
less unit IS being serviced or will be shut down
tor a prolonged period. .Alter such service or
prrdonged shutdown, energize crankcase heater
lor 24 hours before starting compressor.
TIME GUARD® CONTROL
This control protects compressor against short
cycling (Switch A on four-function timer).
FOUR-FUNCTION TIMER
Refer to Fig. 4 — Timer Cycle. The functions are
as follows:
Switch A (Contacts A-Al, A-A2) runs timer motor.
This provides a minimum of 5-1/2 minutes after
compressor stops before it can restart, to prevent
short cycling (Time Guard control).
Switch B (Contacts B-Bl, B-B2) provides 1-second
time delay for part-winding start and also provides
a lock-out function.
Switch D (Contacts D-D 1) provides a 2-1 / 2 minute
bypass of the low-pressure switch at start-up to
prevent nuisance trips under cold-start conditions.
Switch E (Contacts E-El) provides a 35-second by
pass of the oil safety switch (OPS) at compressor
start-up (when OPS is used), if sufficient oil pressure
does not build up in this time, compressor stops.
0 OR 8 MiN.
POSITION DURING UNIT OPERATION-
COMPRESSOR STARTS
1 BBi
1 1
1--------------------------1
H 1—-1 SEC±05
H^SSECiZ
____ Щ_______ I . ............................................. 1
5
7 SEC±4 —И h
■«............^---------- 40SEC15
S DDI
NOTE: BLACK DENOTES CLOSED CONTACTS
Fig. 4 — Timer Cycle
OIL PRESSURE SAFETY SWITCH (OPS)
This control is standard on ЗОНЕ (condenserless)
units (020-030) and is available as an accessory for
30HK units (020-030). Refer to Fig. 5 for field
wiring connections. It is not available for the 015
unit.
The pressure switch is factory set at the following
pressures and should not be adjusted in the field.
SWITCH POSITION
PRESSURE SETTING
Close on rise
9 - 12 psi diff
Open on fall
4 - 6 psi diff
The oil pressure safety switch is wired in parallel
with Switch E of the 4-function timer. This arrange
ment allows approximately 35 seconds for oil pres
sure to reach normal operating level after com
pressor starts. If the oil safety switch does not close
within 35 seconds, the compressor shuts down.
To restart the compressor, the control circuit
ON-OFF switch must be pressed to OFF and then to
ON. The timer will start and after approximately
5-1/2 minutes compressor will start. If normal oil
pressure is established within the next 35 seconds,
the compressor continues to run. If, however, the oil
pressure does not reach a safe level, the compressor
stops at the end of the 35 seconds and locks out.
(’.ли I ION; Di' not attempt to restart the com
pressor tor a second time until the problem has
been determined and corrected.
REMOVE ORANGE Wl RE
OPS — Oil Pressure Safety Switch
TB — Terminal Board
Fig. 5 — Oil Pressure Safety Switch to
Control Box Wiring Connections
(020-030 Only)
LOW LIMIT STOP TAB
Fig. 6 — Safety Thermostat
(No. HH22CC050 Shown)
1090