Table 5 — electrical data; 3-phase, 60-hertz – Carrier 30HK User Manual
Page 6
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Table 5 — Electrical Data; 3-Phase, 60-Hertz
COMPLETE UNIT
VOLTS
Nameplate
208/230*
460
575
COMPRESSOR
06E USAGES
Supply Ränget
187-253
414-508
518 632
UNIT 30
MCA
Max
Fuse
Amps
MCA
Max
Fuse
Amps
MCA
Max
Fuse
Amps
MKW
015
16.4
69
110
34
60
29
50
0537**
020
21.8
79
125
36
60
34
60
2150
025
29.0
103
175
50
90
45
80
7265
030
31.0
115
200
50
90
49
80
7175
015
19.1
80
125
38
60
30
50
C537**
020
25.2
90
150
42
70
38
60
2250
025
31.8
115
200
50
90
45
80
7265
030
35.9
140
250
62
110
53
90
7275
INDIVIDUAL COMPRESSORS
COMPRESSOR
208/230V*
460 V
575 V
06t
Kw
RLA
LRA
MTA
RLA
LRA
MTA
RLA
LRA
MTA
015
0537**
16.4
55
266
77
27
120
37
23
96
31
HK
020
2150
21.8
63
283
88
29
142
40
27
98
37
025
7265
29.0
82
446
114
40
223
56
36
164
50
030
7175
31.0
92
446
128
40
223
56
39
164
54
015
0537**
19.1
64
266
89
30
120
41
24
96
33
HL
020
2250
25.2
72
345
100
33
173
45
30
120
42
025
7265
31.8
92
446
128
40
223
56
36
164
50
030
7275
35.9
112
506
156
49
253
68
42
176
58
KW — Maxi mum Power Input (compressor)
LRA — Locked Rotor Am.ps
MCA -- Mm imum Circuit Amps (for wire sizing). Complies with
National Electrical Code (NEC) Section 430-24.
MKW — Unit power input at operating conditions of 50 F Leaving
Chilled
Water
Temperature
(44
F
Saturated
Suction
Temperature) and 120F (FIK) or 145F (HL) Saturated
Discharge Temperature.
MTA — Must Trip Amps (factory-installed circuit breaker)
RLA — Rated Load Amps
’Compressors in ail models have extended voltage motor.
tUnits are suitable for use on electrical systems where voltage
supplied to the unit terminals is not below or above the range
limits shown.
fPrefix: 2 = 1 electric unloader; C, 7 = 2 electric unloaders.
”30FIK,HL015 models use 06D compressor instead
of 06E compressors.
START-UP AND SERVICE
WAk\lN(j; Shut oil all powur to unit hdorc
proceeding with any ^cr\!ce woik.
Initial Check
Do not attempt to start the liquid chiller even
momentarily until the following steps have been
completed.
1. Check all auxiliary components such as chilled
liquid circulating pump, cooling tower if used,
air handling equipment, or other equipment to
which chiller supplies liquid. Consult manu
facturer’s instructions.
2. Checksafety thermostat. See Safety Thermostat.
3. Determine if there is a refrigerant charge in the
system. Refer to Check Refrigerant Charge.
4. Backseat (open) compressor suction and dis
charge shutoff valves.
5. Open liquid line shutoff valves.
6. Open valves to capillaries of water-regulating
valve (when used).
7. Fill chilled liquid circuit with clean water or
other noncorrosive fluid to be cooled. Bleed
all air out of high points of system.
8. Open supply valve (or fill cooling tower if used)
for condenser cooling water.
9. Set temperature controller.
Check tightness of all electrical connections.
Be sure compressor is floating freely on the
isolation springs. See installation. Step 3.
Check compressor oil (should be visible in
bull’s-eye). Refer to Check Oil Charge.
Be sure crankcase of each compressor is warm
(heaters should be on for 24 hours before start
ing compressors).
Check Refrigerant Charge
IMPORI AN'l; Do not open liquid \al\e or
compressor discharge \al\e until there is a
charge in remainder ol system. .A positive pres
sure will indicate a eharue in svstem.
10
.
11.
12
.
13.
1090