TROUBLESHOOTING GUIDE
SYMPTOMS
1
PROBABLE CAUSE
REMEDY
Compressor does not run !
Power line open
Reset circuit breaker.
!
Control circuit breaker tripped
Check control circuit for ground or
short.
s
Reset breaker.
j Safety tripped
Reset.
1
Tripped power breaker
Check the controls. Find cause of
trip and reset breaker.
Condenser circulating pump not
Power off — restart.
running
Pump binding — free pump.
1
j
Incorrect wiring — rewire.
Pump motor burned out — replace.
Loose terminal connection
Check connections.
Improperly wired controls
Check wiring and rewire.
1
Low line voltage
Check line voltage — determine
location of voltage drop and
remedy deficiency.
j
Compressor motor defective
Check motor winding for open or
short. Replace compressor, if
necessary.
;
i
Seized compressor
Replace compressor.
Compressor cycles on low-
i
Low-pressure control erratic in
Raise differential setting.
pressure control
action
Check capillary for pinches.
1
Replace control.
Compressor suction valve leaking
Replace valve plate.
Compressor suction shutoff valve
partially closed
Open valve.
Low refrigerant charge
Add refrigerant.
Plugged compressor suction
strainer
Clean strainer or replace.
Compressor loses oil
Leak in system
Repair leak.
Mechanical damage (blown piston
or broken discharge valve)
Repair damage or replace
compressor.
Oil trapped in line
Check piping for oil traps.
Crankcase heaters not energized
during shutdown
Check wiring and crankcase
heater relay. Replace heater if
necessary.
Frosted suction line
Expansion valve admitting excess
refrigerant
Adjust expansion valve. Replace
valve if defective.
Compressor cycles on high-
High-pressure control erratic in
Check capillary tube for pinches.
pressure control
action
Set control as required.
Compressor discharge valve
partially closed
Open valve, or replace if defective.
Air in system
Purge.
Condenser scaled
Clean condenser.
Condenser water pump or fans not
operating
Start pump — repair or replace if
defective.
Unit operates long or
Low refrigerant charge
Add refrigerant.
continuously
Control contacts fused
Replace control.
Air in system
Purge.
Partially plugged or plugged
expansion valve or strainer
Clean or replace.
Defective insulation
Replace or repair.
Service load too high
Keep doors and windows closed.
Inefficient compressor
Check valves, replace if necessary.
!4