Refer to Tables 4 and 5 for electrical data on indi
vidual compressors and complete units. Compressor
usage is given in Tables 2 and 5.
ELECTRICAL BOX, CONTROL SECTION
Inside this section are relays, high- and low-
pressure cutouts, low water-temperature cutout,
timer, terminal strips and a 3-step temperature
controller. On the outside (control panel) are con
trol circuit ON-OEF switch, partial load switch
(DLS), compressor run light, safety trip lights and
control circuit fuse. The control panel is hinged to
provide easy access to the controls inside.
^ Table 4 — Unit Voltage and Model Number*
VOLTS
UNIT 30HK.HL
015,020,025,030
208/230
5--
460
6--
575
1--
'Compiete number has 10 digits.
Example: 30HK020530.
UNBALANCED 3-PHASE SUPPLY VOLTAGE
Never operate a motor where a phase imbalance
in supply voltage is greater than 2%. Use the follow
ing formula to determine the % voltage imbalance:
% Voltage Imbalance =
max voltage deviation from average voltage
* *
100 X-
average voltage
Example: Supply voltage is 240-3-60.
* ^
AB = 243 volts
BC = 236 volts
AC = 238 volts
Average Voltage
243 + 236 + 238
717
3
= 239 volts
Determine maximum deviation from average
voltage:
(AB) 243 - 239 = 4 volts
(BC) 239
(AC) 239
236
238
3 volts
1 volt
Maximum deviation is 4 volts.
Determine % voltage imbalance:
A
% Voltage Imbalance = 100 x
239
= 1.7%
This amount of phase imbalance is satisfactory
as it is below the maximum allowable 2%.
IMPOR 1 .-XN'l : li the ■'UppU \oliagc phase im
balance is more than 2((', contact \our h>cal
electric uulits cornpain immcdiateU.
LQUIP GND
Control circuit power is from separate source, Incoming wires are
connected directly to terminals and on TB2.
EQUIPGMD — Equipment Ground
Fig. 3 — Wiring Schematic — Unit and
Control Power Supply
ELECTRICAL BOX, POWER SECTION
The main electrical power supply is brought in
thru the top of the electrical box, on the left-hand
side (see Fig. 1). The hole accommodates up to a
3-in. conduit. Pressure-lug connections on terminal
block are suitable for copper, copper-clad alumi
num or aluminum wire, unless otherwise noted on a
label near the terminal block.
The power section contains: main power terminal
block, compressor circuit breaker with calibrated
magnetic trip (for compressor motor overload and
locked rotor protection), and compressor motor
contactors. The panel over this section is secured
with screws as a safety measure against casual entry
for purposes other than service.