Connect wires having insulated probes to each
capacitor terminal. Touch probes to each side of

run capacitor or to compressor motor terminals R
and S. Start compressor; pull probes away after 3

seconds. Discharge start capacitor.

Run compressor for 10 minutes, then shut off

and allow system to equalize (approximately 5
minutes). Try restart without boost capacitor. If

the compressor does not start after 2 attempts

without the boost capacitor, add an accessory start
capacitor relay package per unit wiring diagrams.

^ Start-Up Sequence, Size 002 Natural Gas Units

The following sequences apply to units with

glow coil pilot ignition, indoor (evaporator) fan
motor time delay relay, and Model A643 heat
motor operated gas valve.

MANUAL SEQUENCE

1. With power off, turn gas valve to “On”

position.

2. Set thermostat selector switch at “Heat” posi­

tion and set thermostat dial a few degrees above
room temperature.

3. Turn power on; automatic sequence begins.

AUTOMATIC SEQUENCE

1. Glow coil pilot ignition system and indoor fan

time delay relay energize.

2. Pilot ignites. (If gas pressure is less than 3

in wg, pilot may not ignite, and if air has not

been bled from gas line, pilot will definitely fail
to ignite. Glow coil cycles on for 15 — 20

seconds and off for 1.52.5 minutes until

conditions are corrected.)

3. Glow coil de-energizes when sensing element of

pilot safety switch is hot enough to indicate a
pilot-proven condition.

4. Main gas valve opens in 1 0 — 1 5 seconds and

main burners ignite.

5. Indoor fan time delay relay closes 30 — 45

seconds after power was turned on; fan motor
starts.

6. Thermostat setting is satisfied and main gas

valve closes in 10 — 14 seconds.

7. Indoor fan motor stops in 1 — 1-1/2 minutes.

^ Start-Up Sequence, Size 003 — 005 Natural Gas

Units

The following sequences apply to units with

spark ignition of pilot, indoor (evaporator) fan
motor time delay relay, and Model A643 heat
motor operated gas valve.

MANUAL SEQUENCE

1. With power off, turn gas valve to “On”

position.

2. Set thermostat selector switch at “Heat”

position and set thermostat dial a few degrees

above room temperature.

3. Turn power on; automatic sequence begins.
AUTOMATIC SEQUENCE

1. Pilot spark ignition system and indoor fan time

delay relay energize.

2. Pilot ignites. (If gas pressure is less than 3

in wg, pilot may not ignite; and if air has not
been bled from gas line, pilot will definitely fail

to ignite. Spark ignition will continue to func­
tion until pilot flame is established. Spark

module electronic circuit will then cut off

spark.)

3. When sensing element of pilot safety switch is

hot enough to indicate a pilot-proven condition
(in 15 — 45 seconds), main gas valve is

energized.

4. Main gas valve opens in 10 — 15 seconds and

main burners ignite.

5. Indoor fan time delay relay closes 30 — 45

seconds after power was turned on; fan motor
starts.

6. Thermostat setting is satisfied and main gas

valve closes in 10 — 14 seconds.

7. Indoor fan motor stops in 1 — 1-1/2 minutes.

Start-Up Sequence, LP Gas Units Without Fan
Purge

The following sequences apply to units with

glow coil pilot ignition, indoor (evaporator) fan
motor time delay relay and Robertshaw Series

7000 BGVE gas valve.

MANUAL SEQUENCE

1. With power off, turn gas valve to “On”

position.

2. Set thermostat selector switch at “Heat” posi­

tion and set thermostat dial a few degrees above
room temperature.

3. Turn power on.

AUTOMATIC SEQUENCE

1. Pilot glow coil and indoor fan time delay relay

energize.

2. Pilot ignites. (If gas pressure is less than 8

in. wg, pilot may not ignite; and if air has not
been bled from gas line, pilot will definitely fail
to ignite Glow coil remains energized until
pilot lights.)

3. Glow coil de-energizes when safety pilot switch

sensing element is hot enougli to indicate a
pilot proven condition.

4. Main gas valve opens; main burners ignite.

5. Indoor fan motor starts in 30 — 45 seconds.

6. Thermostat setting is satisfied; main gas valve

closes.

7. Indoor fan motor stops in I — 1-1/2 minutes.